| 2006-09-05 00:00:00 | DENIED |
| | |
| | 5.STATE PRODUCT APPROVAL REQUIRED |
| | ROOFING.PAGES SUBMITTED ARE NOT STATE |
| | PRODUCT APPROVALS. ALL PRODUCT APPROVALS |
| | SUBMITTED WITH QUALITY ASSURANCE SHALL |
| | HAVE THE FOLLOWING STATE APPROVAL |
| | ATTACHED. |
| | |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A STATE PRODUCT APPROVAL |
| | SHEETS THAT LISTS THE PRODUCT IDENTITY |
| | NUMBER FROM THE STATE. IF THE PRODUCT |
| | DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT |
| | AN APPLICATION FOR LOCAL PRODUCT |
| | APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 6.THOSE PRODUCT APPROVALS WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL.WPB |
| | AMENDMENT TO FBC 106.3.3. |
| | |
| | 8.A DESIGN PROFESSIONAL OR AN OWNER |
| | MUST ELECT ONE OR A COMBINATION OF |
| | LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. |
| | SHOW HOW PLANS WILL COMPLY WITH THE |
| | SECTION(S) SELECTED.2004 FBC EXISTING |
| | BUILDING 301.5 SHOW LEVEL OF ALTERATION |
| | ON PLANS. |
| | |
| | 9.R401.3 DRAINAGE. |
| | SURFACE DRAINAGE SHALL BE DIVERTED TO A |
| | STORM SEWER CONVEYANCE OR OTHER APPROVED |
| | POINT OF COLLECTION SO AS TO NOT CREATE |
| | A HAZARD. LOTS SHALL BE GRADED SO AS TO |
| | DRAIN SURFACE WATER AWAY FROM FOUNDATION |
| | WALLS. THE GRADE AWAY FROM FOUNDATION |
| | WALLS SHALL FALL A MINIMUM OF 6 INCHES |
| | WITHIN THE FIRST 10 FEET. |
| | |
| | 11.SHOW EGRESS FOR EXISTING BEDROOM |
| | WINDOW ADJACENT TO THE ROOM ADDITION. |
| | R-310 |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. SUBMIT ONE COPY OF |
| | OLD PAGES FOR REFERENCE . A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICATION PAGE WHERE THE CHANGES |
| | CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |