| 2006-09-14 00:00:00 | ******DENIED 3RD TIME****** |
| | REFERENCE: FBC-2004 SEC. 402.2 OR |
| | FBRC-2004 SEC. R4101 SWIMMING POOLS: |
| | |
| | THE FOLLOWING INFORMATION IS STILL |
| | REQUIRED FOR PLUMBING PLAN REVIEW: |
| | NOTE: THE SUBMITTED MANUFACTURER SHEETS |
| | WITH THE MET LABORATORIES, INC. |
| | CERTIFICATION RECORD, FILE NUMBER, |
| | E212148 APPROVES THE SUCTION FITTING PER |
| | ASME/ANSI A112.19.8M. ALL SUCTION AND |
| | RETURN PIPING TO THE BADU-JET PUMP SHALL |
| | BE INSTALLED CODE COMPLIANT TO THE |
| | FOLLOWING COMMENTS. |
| | |
| | 1) FBC-2004 SEC 424.2.6.6, OR FBCR-2004 |
| | SEC R4101.6.6 ENTRAPMENT PROTECTION FOR |
| | SUCTION INLETS. (DETAIL REQUIRED) |
| | |
| | 2) FBC-2004424.2.6.6.3, OR FBCR-2004 |
| | SEC R4101.6.6.3 (1,2,3) ENTRAPMENT |
| | AVOIDANCE. (DETAIL REQUIRED) |
| | |
| | 3) FBC-2004 SEC.424.2.6.6.4, OR |
| | FBCR-2004 SEC. R4101.6.6.4 MINIMUM OF |
| | TWO SUCTION INLETS SHALL BE PROVIDED FOR |
| | EA PUMP. SEPARATED BY A MINIMUM OF 3 |
| | FEET OR LOCATED ON TWO DIFFERENT PLANES. |
| | (DETAIL REQUIRED) |
| | |
| | 4) FBC-2004 SEC. 424.6.6 OR FBC-2004 |
| | RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT |
| | PROTECTION FOR SUCTION INLETS. PLEASE |
| | SUBMIT AN ENGINEERED TABLE FOR "VENT |
| | PIPE MAXIMUM LENGTH" INDICATING PUMP |
| | SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH |
| | OF THE 1", 1-1/2" PVC VENT PIPE, FROM |
| | WHERE IT STARTS TO WHERE IT ENDS UP, |
| | COMPLYING WITH THE THREE SECOND RELEASE. |
| | (NOTE: THE VENT TABLE ON THE PRINT ONLY |
| | GOES TO TWO HORSE POWES (2 HP) THE BADU- |
| | JET PUMP PUMP IS FOUR HORSE POWER (4 HP) |
| | PLEASE SUBMIT A TABLE FOR THE HORSE |
| | POWER (4 HP) BADU-JET PUMP. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |
| | |
| | |
| | |
| | |