| 2006-08-10 00:00:00 | ******DENIED****** |
| | REFERENCE: FBC-2004 SEC. 402.2 OR |
| | FBRC-2004 SEC. 4101 SWIMMING POOLS: |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR PLUMBING PLAN REVIEW: |
| | |
| | 1) PLEASE SUBMIT MANUFACTURER'S SPECIFI- |
| | CATIONS FOR THE "BADU-JET" AND PROVIDE |
| | THE FOLLOWING INFORMATION INDICATING THE |
| | SYSTEM IS CODE COMPLIANT. |
| | 2) FBC-2004 SEC 424.2.6.6, OR FBCR-2004 |
| | SEC R4101.6.6 ENTRAPMENT PROTECTION FOR |
| | SUCTION INLETS. (DETAIL REQUIRED) |
| | 3) FBC-2004 424.2.6.6.2, OR FBCR-2004 |
| | SEC R4101.6.6.2 SHOW COMPLIANCE WITH |
| | ANSI/ASME A112.19.8M. PROVIDE MODEL |
| | NUMBER AND MANUF INFO FOR VAC LOCK. |
| | (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES) |
| | 4) FBC-2004424.2.6.6.3, OR FBCR-2004 |
| | SEC R4101.6.6.3 (1,2,3) ENTRAPMENT |
| | AVOIDANCE. (DETAIL REQUIRED) |
| | 5) FBC-2004 SEC.424.2.6.6.4, OR |
| | FBCR-2004 SEC. R4101.6.6.4 MINIMUM OF |
| | TWO SUCTION INLETS SHALL BE PROVIDED FOR |
| | EACH PUMP. SEPARATED BY A MINIMUM OF 3 |
| | FEET OR LOCATED ON TWO DIFFERENT PLANES. |
| | (DETAIL REQUIRED) |
| | 6) FBC-2004 SEC. 424.6.6 OR FBC-2004 |
| | RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT |
| | PROTECTION FOR SUCTION INLETS. PLEASE |
| | SUBMIT AN ENGINEERED TABLE FOR "VENT |
| | PIPE MAXIMUM LENGTH" INDICATING PUMP |
| | SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH |
| | OF THE 1" OR 1-1/2" PVC VENT PIPE, FROM |
| | WHERE IT STARTS TO WHERE IT ENDS UP, |
| | COMPLYING WITH THE THREE SECOND RELEASE. |
| | (NOTE: THE VENT TABLE ON THE DRAWING |
| | ONLY GOES TO 2 HP THE "BADU-JET" PUMP IS |
| | 4 HP) |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |