Plan Review Notes
Plan Review Notes For Permit 06071779
Permit Number 06071779
Review Stop B
Sequence Number 1
Notes
Date Text
2006-08-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)DECLARE BUILDING TYPE, INCLUDING A
 OR B, FBC6.
  
 2.)ARE FIRE SPRINKLER HEAD BEING
 RELOCATED?IF THEY ARE, PROVIDE A
 LAYOUT ON THIS PLAN.IF NOT, NOTE ON
 THE PLAN.FBC*106.3.5.1.1(5).
  
 3.)COVER SHEET, OCCUPANCY SHOULD BE 4,
 NOT LESS THAN FBC TABLE 1004.1.2,
 FBC1004.1.2.
  
 4.)CLARIFY THE REASON FOR THE FIRE
 RATING FOR THE WALL (DOOR INFILL, WALL
 DETAIL 2) EXISTING 2ND FLOOR PLAN A2.01.
  
  