| 2007-02-16 07:02:01 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | NFPA 99C |
| | |
| | FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | 2. OK |
| | |
| | 3. SHTS A2.01 & A2.02 THE FIRST FLOOR |
| | FINISH SCHEDULE FOR ROOMS 103, 104, 118, |
| | (WOMEN, UNISEX HDCP, & MEN TOILET ROOMS) |
| | AS WELL AS ROOMS 202, 205, 208, & 210 |
| | TOILET ROOMS INDICATE PAINTED MR GWB FOR |
| | THE WALLS. PLEASE SHOW HOW THIS COMPLIES |
| | WITH SECTION 1210.2 REQUIREMENTS FOR |
| | WALLS TO BE HARD & NON-ABSORBENT. |
| | ****RESPONSE NOTED, BUT THE FINISH SCHEDULE SHALL |
| | REFLECT THE WALL MATERIAL TO BE INSTALLED. |
| | |
| | 4. SHT A2.01 THE BREAK ROOM SINK AND SHT |
| | A2.02 THE STAFF LOUNGE SINK SHALL BE |
| | ACCESSIBLE. SUBMIT DETAILS SHOWING |
| | COMPLIANCE WITH SECTION 11-4.24 AND ALL SUBSECTIONS. |
| | (FORWARD APPROACH REQUIRED, |
| | AND NO CABINET DOORS ALLOWED IN CLEAR |
| | FLOOR SPACE). |
| | ****RESPONSE NOTED, BUT PLEASE SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | A. 11-4.24.4 SINK DEPTH |
| | B. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | |
| | 5. OK |
| | 6. OK |
| | |
| | 7. SUBMIT A DETAIL SHOWING COMPLIANCE |
| | WITH SECTION 11-4.15 AND ALL SUBSECTIONS |
| | FOR THE DRINKING FOUNTAINS. |
| | ****RESPONSE NOTED, BUT PLEASE SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | A. 11-4.15.2 SPOUT HEIGHT |
| | |
| | 8. SHTS P3.1 & P3.2 AND RPZV BACKFLOW IS |
| | REQUIRED ON THE WATER SERVICE AS CLOSE |
| | TO THE METER AS POSSIBLE, ON PRIVATE |
| | PROPERTY. SECTION 608.13.2 AND MUNICIPAL |
| | ORDINANCE 2853-95. |
| | ****NO RESPONSE, NOT ADDRESSED |
| | |
| | 9. SHT P3.2 FULL OPEN VALVES SHALL BE |
| | INSTALLED ON THE BASE OF EVERY WATER |
| | RISER PIPE, AND ON THE TOP OF EVERY |
| | WATER DOWN-FEED PIPE. SECTION 606.1(3) & 606.1(4). |
| | ****RESPONSE NOTED, BUT THE VALVES ARE NOT SHOWN ON THE |
| | TOP OF EVERY WATER DOWN-FEED PIPE AS REQUIRED. ***CHECK |
| | BOAF INTERPRETATIONS AND IT INDICATED THE VALVES ARE |
| | FOR "UPSIDE DOWN RISERS MORE THAN ONE FLOOR" |
| | |