| 2007-03-01 18:41:51 | *****DENIED***** |
| | |
| | |
| | THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN |
| | REVIEW STILL NEED TO BE ADDRESSED: |
| | |
| | |
| | 02.PLEASE CLEARLY IDENTIFY EMERGENCY LIGHTING IN ALL |
| | COMPONENTS OF MEANS OF EGRESS INCLUDING STAIRS.NO |
| | EMERGENCY LIGHTING NOTICED IN THE STAIRWAYS ON SHEET |
| | A1.01 |
| | |
| | 05.CLASSROOMS AND SIMILAR SPACES SHALL MEET THE |
| | REQUIREMENTS FOR RESCUE WINDOWS.PLEASE INDICATE ON |
| | THE PLAN SHEET A5.01 |
| | |
| | 07.NEW DAMPER INSTALLATIONS SHALL BE DROP TESTED |
| | PRIOR TO THE FINAL INSPECTION.PLEASE INDICATE ON THE |
| | PLANS |
| | |
| | 10.THE FIRE ALARM PANEL SHALL BE ACCESSIBLE FOR |
| | EMERGENCY PERSONNEL.SIGNAGE TO BE DISPLAYED ON |
| | ELECTRICAL ROOM DOOR INDICATING FIRE ALARM CONTROL |
| | PANEL (FACP) INSIDE.PLEASE INDICATE ON THE PLANS |
| | |
| | NEW COMMENTS: |
| | |
| | AA.IT IS INDICATED THAT THE BUILDING IS 100%FIRE |
| | SPRINKLERED.PROVIDE A LAYOUT OF THIS FIRE SPRINKLER |
| | SYSTEM.SEPARATE SHOP DRAWINGS AND PERMITS WILL BE |
| | REQUIRED FOR ANY FIRE SPRINKLER INSTALLATION OR |
| | REMODEL. |
| | |
| | BB.ON SHEET A2.01, IT APPEARS THAT THE EXIT ACCESS |
| | CORRIDOR WILL BE COMPROMISED WHEN THE DOOR(S) TO THE |
| | STORAGE ROOM [109] AND THE MECHANICAL ROOM [102] ARE |
| | OPENED AT THE SAME TIME.AS PER NFPA 101- 7.2.1.4.4* : |
| | DURING ITS SWING , ANY DOOR IN A MEANS OF EGRESS SHALL |
| | NOT LEAVE LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF |
| | AN AISLE, A CORRIDOR, OR A PASSAGEWAY WHEN FULLY OPEN. |
| | |
| | CC.ON SHEET A1.01, VERIFY AND /OR INSTALL A |
| | DIRECTIONAL EXIT SIGN LIGHT INDICATING THE EXIT ONCE |
| | PERSON(S) ARE IN THE CORRIDOR BETWEEN BUIDING #2 AND |
| | BUILDING #1. |
| | |
| | DD. THERE SEEMS TO BE A DISCREPANCY AS REFERNCE TO A AN |
| | EXIT DOOR LOCATED AT THE MIDDLE STAIRWAY ON THE SECOND |
| | FLOOR.IT IS INDICATED AS AN EXIT ON SHEET A1.01, BUT |
| | IS INDICATED ON SHEET E3.02 THAT IT IS NOT AN EXIT. |
| | PLEASE CLARIFY. |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE (ON THE PLAN) EACH COMMENT |
| | WAS ADDRESSED |
| | |
| | |