| Date |
Text |
| 2007-02-04 17:54:34 | ******* UNSAT 2ND REVIEW ****** |
| | |
| | *** PLEASE SEE THERE ARE ITEMS FROM THE PREVIOUS REVIEW |
| | WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW |
| | COMMENTS BASED ON CHANGES IN PLANS AND NEW INFORMATION |
| | AND/OR CHANGES MADE TO PLANS. |
| | |
| | **** IMPORTANT**** |
| | |
| | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | THE PREVIOUS REVIEW WITH A *NO*, *OK* OR *NO/OK*. |
| | |
| | A) A, NO WILL CONTAIN A FURTHER EXPLANATION AS TO WHY |
| | THE COMMENT MAY NOT HAVE BEEN FULLY ADDRESSED WITH THE |
| | PREVIOUS REVIEW NOTE BELOW WITH **PREVIOUS REVIEW NOTE |
| | #1** |
| | |
| | B) A, OK, WILL HAVE NO COMMENTS EXCEPT PERHAPS A |
| | REFERENCE TO SEE ** NEW NOTES*. THE PREVIOUS REVIEW |
| | NOTE WILL BE REMOVED. |
| | |
| | C) A, NO/OK, WILL HAVE FURTHER EXPLANATION AS PART OF |
| | THE COMMENT MAY HAVE BEEN ADDRESSED, HOWEVER NOT ALL. |
| | THE PREVIOUS REVIEW NOTE WILL BE NOTED **PREVIOUS |
| | REVIEW NOTE #1** |
| | |
| | D) NEW NOTES WILL BE ADDED TO THE END AND LABELED ** |
| | NEW NOTES ** |
| | |
| | |
| | |
| | |
| | 1) NOTE: NO, PLEASE SEE NO INFORMATION SPEC ETC WAS |
| | SUBMITTED FOR ANY EQUIPMENT. |
| | 110.3, 90.7, FBC 106.1.2 ETC |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS ON THE |
| | GEN, ATS AND DEPENDING ON PRIME MOVER WHETHER OR NOT A |
| | SUB BASE TANK IS BEING USED ETC. |
| | THIS INFORMATION REQUIRED FOR BOTH. |
| | FBC106.1.2 , NEC110.3,90.8 ETC |
| | |
| | 2) NOTE: NO/OK PLEASE SEE SOMEINFORMATION WAS |
| | SUBMITTED FOR LOCATION HOWEVER AS SPECS ETC WAS NOT |
| | SUBMITTED, REVIEW FOR LOCATION CAN NOT BE CONFIRMED FOR |
| | CODE COMPLIANCE. PLEASE SEE COMMENTS FROM OTHER TRADES |
| | WHICH WILL AFFECT THIS. |
| | PLEASE PROVIDE FLOOD ELEVATION, AND PLEASE KNOW THAT |
| | BEFORE ANY FINAL, A FLOOD ELEVATION CERTIFICATE WILL BE |
| | REQUIRED ALSO. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| | COULD NOT LOCATE A NEW SITE PLAN/SURVEY PLEASE INDICATE |
| | THE GEN LOCATION ON PLANS.IF IN A FLOOD ZONE PLEASE |
| | SEE BUILDING REVIEW COMMENTS AS ELEVATION IS REQUIRED A |
| | 6" MIN ABOVE |
| | BFE. |
| | PLEASE ALSO KNOW A FLOOD ELEVATION CERTIFICATE WILL BE |
| | REQUIRED BEFORE FINAL. |
| | |
| | 3) NOTE: NO/OK, PLEASE PROVIDE CONDUIT AND CONDUCTORS |
| | FROM FPL TRANSFORMER TO GUTTER. PLEASE CORRELATE |
| | EQUIPMENT SCHEDULE WITH RISER. PLEASE SEE NEW COMMENTS |
| | FOR ACCESS AND GROUNDING ELECTRODE CONDUCTOR. |
| | ** SEEMS TO MATCH UP WITH FIGURE 230.9 IN 230.2 OF THE |
| | 2002 NEC HANDBOOK. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| | PLEASE SEE 230.2 AS MORE THAN ONE SERVICE IS BEING |
| | SHOWN FOR THE ONE BUILDING, HOWEVER COULD NOT LOCATE ON |
| | PLANS HOW THE SECOND SERVICE BEING PROPOSED CAN BE |
| | GRANTED UNDER SPECIAL PERMISSION AT THIS TIME. |
| | |
| | 4) NOTE: OK. |
| | |
| | 5) NOTE:NO, PLEASE KNOW THAT AT THIS TIME BASED ON NO |
| | INFORMATION SUBMITTED FOR THE GENERATOR AND THE SERVICE |
| | ENTRANCE CONDUCTORS FROM THE FPL TRANSFORMER TO THE |
| | GUTTER, THE GROUNDING ELECTRODE CONDUCTOR SIZE CAN NOT |
| | BE VERIFIED, PLEASE ALSO SEE 250.66. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| | PLEASECOMPLETE GROUNDING ELECTRODE SYSTEM AS REQUIRED |
| | PER 250.50. |
| | |
| | 6) NOTE: NO, PLEASE KNOW AT THIS TIME THE CIRCUITING |
| | FOR SOME AREAS (STAIRS) WHICH WILL BE UNDER COMMENT #7 |
| | CAN NOT BE VERIFIED. |
| | PLEASE ALSO SEE NEW COMMENTS. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE SHOW ALL CIRCUITING PLANS AND CORRELATE WITH THE |
| | SUBMITTED PANEL SCHEDULES AND PANEL SCHEDULES TO BE |
| | SUBMITTED. |
| | PLEASE SEE 700.12E FOR CIRCUITING OF |
| | EM/EXT LTS. |
| | |
| | 7) NOTE: NO, PLEASE SEE THE STAIR AREAS ARE NOT |
| | COMPLETE AT THIS TIME. PLEASE SEE SOME ARE SHOWN WITH |
| | CONTROLS BY A PHOTO-CELL WHICH IS NOT PERMITTED. PLEASE |
| | SEE OTHER STAIRS WHICH ARE MISSING FROM PLANS ON NORTH |
| | SIDE OF BUILDING. PLEASE SEE THE CENTER STAIRS FROM |
| | SECOND FLOOR TO THE FIRST FLOOR SPECIFICALLY CONTAINS A |
| | NOTE WHICH MENTIONS THIS IS NOT AN EXIT. |
| | PLEASE KNOW THAT DURING AN EMERGENCY CONDITION OR THE |
| | PANIC THAT MAY OCCUR DURING A FIRE ETC, THE NORMAL |
| | BUILDING OCCUPANTS/EMPLOYEES OF THIS SECOND FLOOR WHO |
| | KNOW THIS IS A STAIR WHICH LEADS TO THE FIRST FLOOR |
| | WILL UTILIZE THIS AS AN EXIT. UNLESS THIS DOOR IS |
| | SEALED FROM THE OCCUPANTS SO THAT ACCESS IS NOT |
| | GRANTED, THEN IF ACCESS IS AVAILABLE THEN THIS STAIR |
| | WILL BE REQUIRED TO MEET 7.8.1.3 AND 7.9.2. |
| | PLEASE SEE THE BUILDING REVIEW NOTES WITH RESPECT TO |
| | THE STAIRS PLACING OCCUPANTS BACK INTO A BUILDING OR IN |
| | THIS CASE ANOTHER TENANT SPACE. |
| | PLEASE SEE NO PHOTO-METRICS WERE SUBMITTED FOR MINIMUM |
| | LEVELS FOR EGRESS PATHS ON FIRST FLOOR OR SECOND FLOOR. |
| | PLEASE SUBMIT AND BE AWARE OF ANY CHANGES FROM OTHER |
| | TRADES. CONSULTATION WILL BE FORTH COMING WITH THE FIRE |
| | MARSHAL FOR THE EXITS AND HOW THEY ARE LABELED. |
| | PLEASE ALSO KNOW THAT THE FAILURE OF ANY SINGLE OVER |
| | CURRENT PROTECTION DEVICE OR SWITCHING DEVICE CAN NOT |
| | LEAVE ANY EGRESS PATH IN TOTAL DARKNESS. PLEASE SEE AS |
| | STAIRS AS SHOWN WITH CONTROLS BY TIMERS/PHOTO-CELLS |
| | ETC, THESE DEVICES WOULD CREATE SUCH A LIFE SAFETY |
| | HAZARD. PLEASE SEE THE FAILURE OF THE DEVICE WOULD NOT |
| | TRIGGER THE EMERGENCY LIGHT TO COME ON AS THE CIRCUIT |
| | MAY STILL BE ENERGIZED. |
| | PLEASE SEE THE SELECTION OF THE TYPE OF OVER RIDE |
| | DEVICE SHOULD BE CHOSEN CAREFULLY AND WILL BE REQUIRED |
| | TO CONTAIN A SECOND MEANS OF BACK UP FOR CONTROL. |
| | PLEASE SEE EXIT FROM SOUTH STAIRS STILL DOES NOT |
| | PROVIDE DIRECTIONAL FOR EXIT WHEN EGRESS FROM STAIR |
| | DOOR. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| | PLEASE CLARIFY WHERE THE LIGHTING IS FOR ALL STAIRS. |
| | PLANS APPEAR TO SHOW SOME LIGHTING IN CENTER STAIRWAY, |
| | HOWEVER NOT FOR OTHERS. PLEASE ALSO SEE STAIRS ARE |
| | BEING SHOWN ON TIMED SCHEDULE HOWEVER CONTROLS FOR |
| | LIGHTING OUTSIDE TIME SCHEDULING SHALL BE PROVIDED BY A |
| | MIN OF TWO METHODS,(OCCUPANCY SENSORS ON LTS, OCCUPANCY |
| | SENSORS IN STAIRS , TIMED DOOR CONTACTS ETC.) PLEASE |
| | KNOW, ENTERING INTO THE EXIT STAIR WAY AND HAVING THE |
| | LIGHTING SHUT OFF AND LEAVE IN TOTAL DARKNESS IS A LIFE |
| | SAFETY ISSUE. |
| | PLEASE ALSO PROVIDE BATTERY BACK UP FIXTURES. |
| | PLEASE ALSO SEE A MINIMUM OF 10 FT CANDLES IS REQUIRED |
| | UNDER NORMAL AND CAN BE RATED DOWN TO 1FT UNDER EM |
| | CONDITIONS. PLEASE PROVIDE PHOTO-METRICS. (CAN BE |
| | TYPICAL) |
| | PLEASE SEE EXITING FROM STAIRS ON SOUTH SIDE OF |
| | BUILDING SHOWS EGRESS INTO A HALL WAY WITH NO EXIT |
| | DIRECTIONAL. |
| | PLEASE SEE NFPA-101 |
| | 7.8,7.8.1.3,7.9,7.9.2.2 ETC. |
| | PLEASE SEE FIREREVIEW COMMENTS. |
| | FBC CHAPTER 13 |
| | |
| | 8) NOTE: OK/NO, PLEASE SEE THE ELEVATOR MACHINE ROOM IS |
| | NOW SHOWN; HOWEVER PLEASE SEE 620.23 AND 24 FOR |
| | REQUIRED DEDICATED CIRCUITS. PLEASE SEE THESE ARE ON |
| | THE SAME CIRCUIT. |
| | PLEASE ALSO SEE NEW NOTES FOR ELEVATOR DISCONNECT. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | COULD NOT LOCATE THE ELEVATOR MACHINE RM.? PLEASE SEE |
| | 620.23, 620.24, |
| | 700.16. ETC |
| | COULD NOT LOCATE THE MIN CIRCUITING FOR LTS, RECEPTS , |
| | CAB ETC. |
| | PLEASE ALSO KNOW, A BATTERY BACK UP FIXTURE OF SOME |
| | SORT WILL BE REQUIRED IN THE ELEVATOR EQUIPMENT RM. |
| | 7.8,7.9, 700.16 |
| | |
| | 9) NOTE: OK. |
| | |
| | 10) NOTE: NO, PLEASE SEE PLANS INDICATE GFI BEING |
| | PROVIDED WITH THE EQUIPMENT WHICH IS NOT COMMON. PLEASE |
| | PROVIDE EQUIPMENT INFORMATION SHOWING THE TAP |
| | CONDUCTORS, OVER CURRENT PROTECTION, MEANS OF |
| | DISCONNECT ETC. |
| | IF THIS IS NOT THE CASE, PLEASE SUBMIT AND SHOW THE |
| | CIRCUITING FOR ALL ROOF TOP EQUIPMENT. CAN NOT RELY ON |
| | THE EQUIPMENT LEGEND AND PANEL SCHEDULES. |
| | 110.3, 90.7, 240.21, 240.4, 310.16 ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE SEE MISSING CIRCUITING ON ROOFTOP PLANS FOR |
| | UNITS AND GFI RECEPTS FOR ROOFTOPQUIPMENT. |
| | 230.63,210.8 |
| | |
| | 11) NOTE: OK. |
| | |
| | 12) NOTE: OK. |
| | |
| | 13) NOTE: NO, PLEASE SEE THERE ARE ROOMS ON PLANS WHICH |
| | DO NOT INDICATE ANY DESIGNATIONS. PLEASE SEE NEW NOTES |
| | WITH RESPECT TO PANEL SCHEDULE(S) AND CIRCUITING ON |
| | PLANS. |
| | PLEASE SEE NEW NOTES FOR ROOMS WITH PANELS AND OTHER |
| | ELECTRICAL ROOMS. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| | PLEASE PLACE ALL ROOM AND AREA DESIGNATIONS ON PLANS. |
| | UNABLE TO VERIFY SOME OF THESE ROOMS AT THIS TIME. |
| | |
| | 14) NOTE:NO? PLEASE SEE AS SOME OF THE ROOM |
| | DESIGNATIONS ARE MISSING IT IS NOT CLEAR IF THERE IS AN |
| | IT ROOM.IT DOES NOT APPEAR THERE WILL BE TRUE IT |
| | ROOM, HOWEVER PLEASE COMPLETE NOTE #13 ABOVE AND THIS |
| | SHOULD ALLEAVIATE THIS COMMENT. |
| | ** PREVIOUS REVIEW NOTE REVIEW #1 |
| | PLEASE SEE PLANS MENTIONS "IT" ROOM ON SECOND FLR. |
| | PLEASE SEE NFPA-75 AND NFPA-70(NEC) 645 FOR |
| | REQUIREMENTS. |
| | |
| | 15) NOTE: OK. |
| | |
| | 16) NOTE: NO, PLEASE SEE THERE ARE A FEW NOTES |
| | PERTAINING TO THE ENERGY CALCULATIONS AND LIGHTING |
| | PERFORMANCE CALCULATIONS. |
| | A ) PLEASE SEE THE ENERGY CALCULATIONS ARE THE ONES |
| | PREVIOUSLY SUBMITTED WHICH WERE SIGNED BY THE PREVIOUS |
| | BUILDING CONTRACTOR WHICH IS NO LONGER APART OF THIS |
| | PROJECT. PLEASE OBTAIN NEW SIGNATURES. |
| | B) PLEASE SEE THAT NO LIGHTING PERFORMANCE TABLES, |
| | CHARTS, LEVELS ETC WERE SUBMITTED AND METHOD *A* DOES |
| | NOT PROVIDE THIS INFORMATION. PLEASE ALSO CLARIFY THE |
| | USE OF METHOD *A*, AS THE A-SHEETS INDICATE A LEVEL 3 |
| | ALTERATION, HOWEVER PLEASE SEE NEW NOTES FOR THIS AS |
| | THIS IS A CHANGE IN OCCUPANCY AND DOES APPEAR TO FALL |
| | UNDER A LEVEL 3 ALTERATION. PLEASE SEE FBC CHAPTER |
| | 13-101.3 |
| | C) PLEASE SEE SOME AREAS IN THE INPUT DATA REPORT WHICH |
| | INDICATES MANUAL CONTROLS, HOW IS THIS POSSIBLE IF ALL |
| | LIGHTING CONTAINS AUTOMATED CONTROLS? |
| | |
| | **PLEASE SEE NEW NOTES PERTAINING TO LIGHTING |
| | CONTROLS. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE SEE 13-415.2.ABC.1, TABLES 415.2.C.1, 415.2.B.1 |
| | |
| | 17) NOTE: NO, PLEASE SEE RISER SHOWS THE SECOND FLOOR |
| | ATS AS BEING LABELED WITH THE SAME DESIGNATION AS THE |
| | FIRST FLOOR ATS. |
| | PLEASE SEE THE ELEVATOR CIRCUITS WHICH IS SHOWN AS |
| | 225AMPS IN PANEL M-2, YET THE EQUIPMENT LEGEND SHOWS |
| | 200AMP DISCONNECT? |
| | PLEAS ADJUST AND COORDINATE. |
| | 240.4, 310.16. |
| | 106.1.2 ADMIN SECTION. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| | PLEASE SEE "EQUIPMENT CO-ORDINATION SCHEDULE", PLEASE |
| | SEE MAINS DISCONNECTS WHICH ARE INDEED MAINS AND PLEASE |
| | ALSO SEE MAINS FOR EACH FLR ALSO BEING LABELED AS |
| | "MAINS" 1 AND 2. |
| | PLEASE ADJUSTED IDENTIFICATION ACCORDINGLY. |
| | 230.2E |
| | |
| | |
| | ***** NEW NOTES ***** |
| | |
| | 18) NOTE: PLEASE SEE ACCESS FOR THE MAIN DISCONNECT AND |
| | GENERATOR DISCONNECT AND EQUIPMENT FOR THE POWER FOR |
| | THE SECOND FLOOR TENANT APPEARS TO ONLY BE ACCESSED |
| | THROUGH THE FIRST FLOOR TENANT SPACE. PLEASE SEE A |
| | REDESIGN WILL BE REQUIRED AS ACCESS TO THIS EQUIPMENT |
| | IS REQUIRED FOR THIS 2ND FLOOR TENANT AT ALL TIMES. |
| | (OUTSIDE DOOR) ETC 240.24B ETC |
| | |
| | 19) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO |
| | ROOM DESIGNATIONS, PLEASE SEE ROOM/AREA WHERE PANEL |
| | *S3* IS LOCATED. |
| | 110.26, 408.7, 240.24D |
| | |
| | 20) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, |
| | .1.2 AND .1.3. |
| | A) PLEASE PROVIDE THE TIME OF DAY SCHEDULING FOR LC |
| | PANELS. |
| | B) PLEASE SEE WOMEN'S BATHROOM ON FIRST FLOOR WHICH |
| | CONTAINS A DEVICE*S UC*WHICH IS NOT ON ANY SYMBOL |
| | LEGEND. ? |
| | C) PLEASE SEE A SWITCH WITH A DESIGNATION OF *S M* |
| | WHICH IS NOT ON ANY SYMBOL LEGEND.? |
| | D) PLEASE PROVIDE ALL MAXIMUM TIMES ON OVER |
| | RIDES/OCCUPANCY SENSORS/TIMER TYPE DEVICES. |
| | E) PLEASE SEE OC TYPE IS 30 MINUTES MAX AND TIMER TYPES |
| | ARE 4HRS MAX. |
| | F) PLEASE SEE HALL AREAS WHICH CONTAIN OVER RIDE |
| | DEVICES WHICH ARE SHOWN AS *S M*, DO THESE PROVIDE |
| | COMPLETE COVERAGE OF THE ENTIRE HALL WAY AREA BEING |
| | OVER RIDDEN WHEN TIMED SCHEDULING IS OFF. AS THIS |
| | DEVICE APPEARS TO BE A MOTION TYPE DEVICE, PLEASE |
| | VERIFY AS LOCATING *NIGHT LIGHTS* ON PLANS COULD NOT BE |
| | FOUNDIN THE EVENT OF THESE DEVICES NOT BEING ABLE TO |
| | DETECT THE OCCUPANT AND LEAVING THE OCCUPANT IN TOTAL |
| | DARKNESS. |
| | PLEASE SEE LS 101 7.8 AND 7.9 FOR THIS AS NOTED ABOVE |
| | IN THE PREVIOUS REVIEW NOTE #7. |
| | |
| | 21) NOTE: PLEASE SEE PANEL SCHEDULE SHOULD BE MORE |
| | DETAILED FOR ROOMS AND AREAS WHICH THEY FEED. PLEASE |
| | SEE THE BELOW IS TAKEN FROM THE COMMENTARY FROM THE |
| | HANDBOOK IN 408.4. PLEASE SEE ALL THE CIRCUITS WHICH |
| | ONLY INDICATE *RECEPTACLES* AND NOT TO ANY ROOMS/OFFICE |
| | DESIGNATIONS. |
| | * REQUIRES THAT THE IDENTIFICATION FOR EVERY CIRCUIT |
| | SUPPLIED BY A PANELBOARD OR SWITCHBOARD BE LEGIBLE AND |
| | CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE |
| | CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE |
| | MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE, |
| | SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN |
| | THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS. |
| | IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH |
| | CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE |
| | IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING |
| | ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP |
| | RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES |
| | CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR |
| | ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL |
| | REQUIRED BY THIS SECTION. |
| | |
| | 22) NOTE: PLEASE SEE THAT ANY COMMON AREA BRANCH |
| | CIRCUITS SHALL BE REQUIRED TO BE FED FROM A HOUSE PANEL |
| | OF SOME TYPE, NOT FROM A TENANT PANEL. |
| | *GEN ROOM*, *MAIN ELECTRICAL ROOM*. |
| | 104.6 FBC ADMIN SECTION. |
| | |
| | 23) NOTE: PLEASE SEE ATTACHED NOTICE TO FS 553.80(2)(B) |
| | IS GIVEN AT THIS TIME WITH RESPECT TO CODE COMMENTS. |
| | PLEASE KNOW THAT THIS IS ONLY GIVEN AS A NOTICE AT THIS |
| | TIME. |
| | |
| | ** PLEASE KNOW AS THERE IS INFORMATION NOT YET |
| | SUBMITTED, COMMENTS MAY NOT BE COMPLETE AT THIS TIME. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |