| Date |
Text |
| 2007-02-28 14:40:07 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 06071 |
| | ADD: |
| | CONT: |
| | TEL: (561)###-#### |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | NOTE-- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1ST REQUEST) PER ARTICLE 13 OF THE UNIFIED LAND |
| | DEVELOPMENT |
| | CODE, IMPACT FEES ARE PAYABLE ON THE CHANGE OF USE |
| | (OCCUPANCY). |
| | BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 2-5 ) COMPLIED. |
| | |
| | 6) 2ND REQUEST, PROVIDE DETAILS FOR ALL STRUCTURAL |
| | MODIFICATIONS TO THE |
| | EXTERIOR WALLS, (INFILL OF ELEVATOR EXTERIOR DOORS, AND |
| | MODIFICATIONS TO |
| | ACCEPT NEW DOORS & WINDOWS, ETC). |
| | |
| | 6A)STRUCTURAL SHEETS S-0.1-S.2ARE NOT SIGNED NOR |
| | SEALED. |
| | PLANS, SPECIFICATIONS, REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND |
| | BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 6B) STRUCTURAL SHEET S0.1 DESIGN LOADS INDICATE ASCE |
| | 7-98 CORRECT TO THE |
| | ASCE 7-02. |
| | |
| | 6C) S.01 HAS A NOTE INDICATING THIS TO BE A THRESHOLD |
| | BUILDING. PLEASE TAKE NOTE OF 553.71(7) "THRESHOLD |
| | BUILDING" MEANS ANY BUILDING WHICH IS GREATER THAN 3 |
| | STORIES OR 50 FT IN HEIGHT, OR WHICH HAS AN ASSEMBLY |
| | OCCUPANCY CLASSIFICATION AS DEFINED IN THE FLORIDA |
| | BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA AND AN |
| | OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. |
| | THIS BUILDING DOES NOT QUALIFY AS A THRESHOLD |
| | BUILDING. |
| | |
| | 6D) STRUCTURAL PLANS ALSO INDICATE A SHELL PERMIT DATED |
| | 12-19-06 SEE ATTACHMENT NO SUCH PERMIT APPLICATION. |
| | |
| | 7) 2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) FIXED WINDOWS STOREFRONT |
| | B) WINDOWS- HORIZONTAL SLIDERS |
| | C) WINDOWS- CASEMENT |
| | D) EXTERIOR HOLLOW METAL DOORS WITH VIEW PANELSLARGE |
| | MISSLE IMPACT TESTING |
| | E) GLAZED DOORS ALUMINIUM/ GLAZED PANELS/ W SIDE |
| | LITES |
| | F)OVERHEAD DOOR |
| | G)ROOF ACCESS HATCH |
| | H) ROOF ASSEMBLIES. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 8) 2ND REQUEST, |
| | WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 9-12) COMPLIED. |
| | |
| | 13) GENERATOR TO BE UNDER A SEPERATE PERMIT. |
| | |
| | 14& 15 ) COMPLIED. |
| | |
| | 16) DOORS STILL NOT IN COMPLIANCE WITH :11-4.13.6 |
| | MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARANCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARANCES SHALL BE |
| | CLEAR & LEVEL. |
| | DOORS: 206A, 208A & 217C. |
| | |
| | 17) COMPLIED. |
| | |
| | 18) 2ND REQUEST,FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| | THE COURT. |
| | NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| | NOT ACTUALLYCOMMENCED WITHIN |
| | 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE IS |
| | NULL & VOID. NOTE: 713.13(6)THE POSTING |
| | OF THE NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE |
| | BEFORE THE FIRST INSPECTION. |
| | |
| | NEW COMMENTS: |
| | 19)SHEET A2.01 & A2.02 BOTH INDICATE THE REQUIREMENT |
| | FOR SMOKE RATED CORRIDORS SINCE THIS IS A FIRE |
| | SPRINKLERD |
| | BUILDING. THESE SHEETS INDICATE A "P1" WALL WHERE AS |
| | THE SMOKE RESISTANT WALLS ARE TO BE A "P2".TABLE |
| | 1016. |
| | |
| | 20) SHEET A2.01 ROOM 110 IS LABELED A "CHILL ZONE" |
| | AREAS WHERE NORMALLY SUBJECT |
| | TO STUDENT OCCUPANCY SHALL ALSO REQUIRE EMERGENCY |
| | ESCAPE AND RESCUE WINDOWS, SEE 1025.4.1. |
| | |
| | 21) FLAT ROOF THE REPORT SUBMITTED, THIS ROOF IS |
| | MISSING OR NOT IN |
| | COMPLIANCE WITH THE FOLLOW ITEMS: |
| | |
| | __X_ CONTRACTOR DID NOT PROVIDE THE MEAN |
| | |
| | ROOF HEIGHT. |
| | |
| | ___ CONTRACTOR DID NOT INDICATE THE ROOF |
| | PITCH. |
| | |
| | _X__ CONTRACTOR FAILED TO INDICATE WHICH |
| | SYSTEM TO BE USED. |
| | |
| | _X__ THE SYSTEM PROVIDED HAS A LOW |
| | PRESSURE FOR ZONE ___ . |
| | |
| | _X__ THE SYSTEM PROVIDED STATES |
| | LIMITATION# 7, SHOULD THE FASTENER |
| | RESISTANCE BE LESS THAN THAT |
| | REQUIRED, AS DETERMINED BY THE |
| | BUILDING OFFICIAL, A REVISED |
| | FASTENER SPACING, PREPARED , SIGNED |
| | AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER, REGISTERED |
| | ARCHITECT OR REGISTERED ROOF |
| | CONSULTANT MAY BE SUBMITTED. |
| | |
| | _X__THE SYSTEM PROVIDED INDICATES |
| | LIMITATION# 9, NO ENHANCED |
| | FASTENING ALLOWED. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |