| Date |
Text |
| 2007-12-20 15:46:00 | REVISION DENIED |
| | REFERENCE: FBC-2004 CHAPTER 1 |
| | NFPA 99C-99 |
| | |
| | 1. SUBMITISOMETRIC RISER DIAGRAMS FOR THE VACUUM |
| | PIPING AND THE COMPRESSED AIR PIPING. SECTION |
| | 106.3.5.1.3. |
| | |
| | 2. SHT P-3.3 THE VACUUM SYSTEM SHALL COMPLY WITH |
| | SECTION 4-5.2 AND ALL SUBSECTIONS. SHOW COMPLIANCE WITH |
| | THE FOLLOWING: |
| | A. 4-5.2.1.1 SERVICE INLETS SHALL BE EITHER A SHUT |
| | OFF VALVE WITH A THREADED FEMALE PIPE CONNECTOR, OR A |
| | QUICK-CONNECT FITTING WITH A SINGLE CHECK VALVE. |
| | B. 4-5.2.1.2 LIQUID/AIR SEPARATOR (EQUIPMENT SHALL BE |
| | OBTAINED FROM AND BE INSTALLED UNDER THE SUPERVISION OF |
| | A MANUF. OR SUPPLIER FAMILIAR WITH PROPER PRACTICES FOR |
| | ITS CONSTRUCTION AND USE). (SEE FIGS. 4-5.2.1.2 A THRU |
| | D. |
| | C. 4-5.2.1.3 LIQUIDS FROM A LEVEL VACUUM SYSTEM, PER |
| | 4-5.2.2, SHALL BE DIRECTLY CONNECTED TO THE SANITARY |
| | DRAINAGE SYSTEM. (SEE FIGURES 4-5.2.1.3(A) THRU(B). |
| | (SEE ATTACHED SHEETS). (SHOWN AS INDIRECT CONNECTION ON |
| | FIGURE 2 SHT P-3.3). |
| | D. 4-5.2.1.5 EXHAUST SHALL BE LOCATED REMOTE FROM ANY |
| | DOOR, WINDOW, AIR INTAKE, OR OTHER OPENING IN THE |
| | BUILDING ETC. |
| | E. 4-5.2.1.6 EXHAUST PROTECT AGAINST ENTRY OF INSECTS |
| | ETC. |
| | F. 4-5.2.2.1 CLEANOUTS REQUIRED. |
| | G. 4-5.2.2.3 CLEANOUTS REQUIRED. |
| | H. 4-5.2.2.5 PIPING TO BE SLOPED . |
| | |
| | 3. SHT P-3.3 THE GAS-POWERED DEVICES LEVEL 3 SHALL |
| | COMPLY WITH SECTION 4-5.1.1 AND ALL SUBSECTIONS. SHOW |
| | COMPLIANCE WITH THE FOLLOWING: |
| | A. 4-5.1.1.3(A)(D)(E)(G)(H) INTAKE SHALL BE FROM THE |
| | OUTSIDE WHEN PRACTICAL. |
| | B. 4-5.1.3.3(A) THRU (I) |
| | |
| | 4. SEE ATTACHED SHEETS FOR TYPICAL LEVEL 3 VACUUM AND |
| | AND GAS POWERED DEVICES SUPPLY SYSTEMS. |
| | |
| | 5. A SEPARATE MED-GAS PERMIT IS REQUIRED. |
| | CERTIFICATIONS FOR THE QUALIFER, THE BRAZER, & |
| | INSTALLER ARE REQUIRED WHEN APPYING FOR THE PERMIT. |
| | PICTURE IDENTIFICATION IS REQUIRED ON THE |
| | CERTIFICATIONS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |