| Plan Review Notes For Permit 06071722 |
| Permit Number |
06071722 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-06-11 11:54:47 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | 1. SHT P-5.1 INDICATES THE GAS METERS INSIDE THE | | | STRUCTURE. THIS IS HIGH PRESSURE AND PER SECTION 402.6 | | | THE MAXIMUM DESIGN OPERATING PRESSUREFOR PIPING | | | SYSTEMS LOCATED INSIDE BUILDINGS IS 5 PSI.PLEASE | | | INDICATE THE SUPPLY PRESSURE TO THE METERS AND/OR MOVE | | | THE METERS OUTSIDE THE BUILDING AND RECHECK THE TOTAL | | | DEVELOPED LENGTH OF THE GAS PIPING TO THE FURTHEST | | | GENERATOR. | | | | | | NOTE: THERE WAS NO INDICATION THAT A NEW PLUMBING SHEET | | | AS ADDED AFTER THE FIRST REVIEW IN THE COMMENT | | | RESPONSES SO SHT P-5.1 WAS OVERLOOKED IN THE SECOND | | | REVIEW.THAT IS WHY THE GAS REVIEW COMMENTS WERE NOT | | | INDICATED ON THE SECOND REVIEW. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|