| Date |
Text |
| 2006-08-14 00:00:00 | ******** UNSAT ********** |
| | |
| | 1) NOTE: PLEASE SUBMIT ALL MANUFACTURES |
| | SPECS/CUT SHEETS ON THE GEN, ATS AND |
| | DEPENDING ON PRIME MOVER WHETHER OR NOT |
| | A SUB BSAE TANK IS BEING USED ETC. |
| | THIS INFORMATION REQUIRED FOR BOTH. |
| | FBC106.1.2 , NEC110.3,90.8 ETC |
| | |
| | 2) NOTE; PLEASE INDICATE THE GEN |
| | LOCATION ON PLANS.IF IN A FLOOD ZONE |
| | PLEASE SEE BUIDLING REVIEW COMMENTS AS |
| | ELEVATION IS REQUIRED A 6" MIN ABOVE |
| | BFE. |
| | PLEASE ALSO KNOW A FLOOD ELEVATION |
| | CERTIFICATE WILL BE REQUIRED BEFORE |
| | FINAL. |
| | |
| | 3) NOTE: PLEASE SEE 230.2 AS MORE THAN |
| | ONE SERVICE IS BEING SHOWN FOR THE ONE |
| | BUILDING, HOWEVER COULD NOT LOCATE ON |
| | PLANSHOW THE SECOND SERVICE BEING |
| | PRPOSED CAN BE GRANTED UNDER SPECIAL |
| | PERMIISION AT THIS TIME. |
| | |
| | 4) NOTE: PLEASE CLARIFY ON PLANS WHERE |
| | M1 AND M2 ARE? CAN NOT VERIFY |
| | 240.24,110.26 ETC. |
| | 106.1.2 FBC. |
| | |
| | 5) NOTE: PLEASECOMPLETE GROUNDING |
| | ELECTRODE SYSTEM AS REQUIRED PER 250.50. |
| | |
| | 6) NOTE: PLEASE SHOW ALL CIRCUITING |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULES AND PANEL SCHEDULES TO |
| | BE SUBMITTED. |
| | PLEASE SEE 700.12E FOR CIRCUITING OF |
| | EM/EXT LTS. |
| | |
| | 7) NOTE: PLEASE CLARIFY WHERE THE |
| | LIGHTING IS FOR ALL STAIRS . PLANS |
| | APPEAR TO SHOW SOME LIGHTING INCENTER |
| | STAIRWAY,HOWEVER NOT FOR OTHERS. PLEASE |
| | ALSO SEE STAIRS ARE BEING SHOWN ON TIMED |
| | SCHEDULE, HOWEVER CONTROLS FOR LIGHTING |
| | OUTSIDE TIME SCHEDULING SHALL BE |
| | PROVIDED BY A MIN OF TWO |
| | METHODS,(OCCUPANCY SENSORS ON LTS, |
| | OCCUPANCY SENSORS IN STAIRS , TIMED DOOR |
| | CONTACTS ETC.) PLEASE KNOW, ENTERING |
| | INTO THE EXIT STAIR WAY AND AHAVING THE |
| | LIGHTING SHUT OFF AND LEAVE IN TOTAL |
| | DARKNESS IS A LIFE SAFETY ISSUE. |
| | PLEASE ALSO PROVIDE BATTERY BACK UP |
| | FIXTURES. |
| | PLEASE ALSO SEE A MINIMUM OF 10 FT |
| | CANDLES IS REQUIRED UNDER NORMAL AND CAN |
| | BE RATED DOWN TO 1FT UNDER EM |
| | CONDITIONS. PLEASE PROVIDE |
| | PHOTO-METRICS. (CAN BE TYPICAL) |
| | PLEASE SEE EXSTING FROM STAIRS ON SOUTH |
| | SIDE OF BUILDING SHOWS EGRESS INTO A |
| | HALL WAY WITH NO EXIT DIRECTIONALS. |
| | PLEASE SEE NFPA-101 |
| | 7.8,7.8.1.3,7.9,7.9.2.2 ETC. |
| | PLEASE SEE FIREREVIEW COMMENTS. |
| | FBC CHAPTER 13 |
| | |
| | 8) NOTE: COULD NOT LCATE THE ELEVATOR |
| | MACHINE RM.? PLEASE SEE 620.23,620.24, |
| | 700.16. ETC |
| | COULD NOT LOCATE THE MIN CIRCUTING FOR |
| | LTS, RECEPTS , CAB ETC. |
| | PLEASE ALSO KNOW, A BATTERY BACK UP |
| | FIXTURE OF SOME SORT WILL BE REQUIRED IN |
| | THE ELEVATOR EQUIPMENT RM. |
| | 7.8,7.9, 700.16 |
| | |
| | 9) NOTE: PLEASE SEE EQUIPMENT LIST, |
| | MENTIONS PANELBOARD/CIRCUIT AS FPL, |
| | HOWEVER PLEASE KNOW EQUIPMENT AS SHOWN |
| | IS NOT BY FPL FOR MAINS, METER ETC. |
| | 106.1.2 FBC |
| | |
| | 10) NOTE: PLEASE SEE MISSING CIRCUITING |
| | ON ROOFTOP PLANS FOR UNITS AND GFI |
| | RECEPTS FOR ROOFTOP EQUIPMENT. |
| | 230.63,210.8 |
| | |
| | 11) NOTE: PLEASE VERIFY WHERE LOAD |
| | CALCUALTIONS ARE SHOWN AND ALL |
| | CONTINUOUS LOADS/LARGEST MOTORS AT |
| | 125%.220.3,220.10,220.11,220.13,215.3, |
| | 230.42 ETC |
| | |
| | 12) NOTE: PLEASE PLEASE PROVIDE PANEL |
| | SCHEDULES FOR LLC1, AND LLC2 AND |
| | CORRELATE WITH THE CIRCUITING PLANS. |
| | FBC 106.1.2 |
| | |
| | 13) NOTE: PLEASE PLACE ALL ROOM AND AREA DESIGNATIONS |
| | ON PLANS. |
| | UNABLE TO VERIFY SOME OF THESE ROOMS AT |
| | THIS TIME. |
| | |
| | 14) NOTE: PLEASE SEE PLANS MENTIONS "IT" |
| | ROOM ON SECOND FLR. PLEASE SEE NFPA-75 |
| | AND NFPA-70(NEC) 645 FOR REQUIREMENTS. |
| | |
| | 15) NOTE: PLEASE SEE 620.51 FOR |
| | DISCONNECTING OF ELEVATOR EQUIPMENT. AS |
| | ROOM IS NOT VERIFIED AT THIS TIME, NOT |
| | SURE WHERE THIS DISCONNECTING MEANS IS? |
| | |
| | 16) NOTE: PELASE SEE 13-415.2.ABC.1, |
| | TABLES 415.2.C.1, 415.2.B.1 |
| | |
| | 17) NOTE: PLEASE SEE "EQUIPMENT |
| | CO-ORDINATION SCHEDULE", PLEASE SEE |
| | MAINS DISCONNECTS WHICH ARE INDEED MAINS |
| | AND PLEASE ALSO SEE MAINS FOR EACH FLR |
| | ALSO BEING LABELED AS "MAINS" 1 AND 2. |
| | PLEASE ADJUSTED IDENTIFICATION |
| | ACCORDINLGY. |
| | 230.2E |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |