| Plan Review Notes For Permit 06071689 |
| Permit Number |
06071689 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-07-28 00:00:00 | ******* UNSAT ********* | | | | | | 1) NOTE: PLEASE COMPLETE RISER WITH ALL | | | BRNACH CIRCUIT CONDUCTOR SIZES AS | | | REQUIRED. PLEASE LIST THE OCP FOR EACH | | | UNIT BEING FED. | | | 240.4,310.16, 408.4 | | | FBC 106.1.2 | | | | | | 2) NOTE: PLEASE 220.31B FOR MIN LOAD | | | CALCULATIONS TO BE DONE. | | | PLEASE SEE NO SM APPL CIRCUITS SHOWN | | | ETC.220.16 | | | PLEASE SEE 220.18 FOR MIN KW FOR DRYER. | | | | | | 3) NOTE: PLEASE SEE MISSING NEW OR | | | EXISTING GFI FOR CU. | | | 210.63 | | | | | | 4) NOTE: PLEASE SEE MISSING THE PRINTED | | | NAME AND SIGNATURE OF THE PRESON | | | RESPONSIBLE FOR SAID PLANS/DESIGN. | | | FBC106.1.2 ADMIN SECT. | | | | | | 5) NOTE: PLEASE SUBMIT TWO SETS, ONE | | | WILL COME BACK FOR INSPECTION AND ONE | | | WILL REMAIN ONFILE. | | | 106.1 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | |
|