| Date |
Text |
| 2006-09-15 00:00:00 | ******DENIED 2ND TIME***** |
| | |
| | REFERENCE: FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | |
| | THE FOLLOWING INFORMATION IS STILL |
| | REQUIRED FOR GAS PLAN REVIEW DUE TO THE |
| | FACT THAT THE PREVIOUS COMMENTS HAVE NOT |
| | BEEN ADDRESSED: |
| | |
| | 1. MORE INFOMATION IS REQUIRED ON THE |
| | TYPE OF MATERIAL THAT IS BEING INDICATED |
| | ON THE GAS RISER DIAGRAM. WHAT IS "CTS"? |
| | PLEASE CLARIFY FOR THE RESUBMITTAL. |
| | 2. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | NOTE: PLEASE INDICATE THE BTU LOAD LOAD |
| | OF THE GENERATOR ON THE ISOMETRIC RISER |
| | DIAGRAM FOR THE RESUBMITTAL. |
| | 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 |
| | NOTE: PLEASE SUBMIT MANUFACTURER CUT |
| | SHEETS OF THE 1ST AND 2ND STAGE |
| | REGULATORS. |
| | 4.PLEASE INDICATE WHICH MODEL GENERATOR |
| | IS BEING USED IN THE MANUFACTURER |
| | ISTALLATION AND OWNERS MANUAL ON PAGE 6 |
| | SO THAT THE GENERATOR BTU LOADS CAN BE |
| | VERIFIED. |
| | 5. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | NOTE: THERE ARE NO MEASUREMENTS |
| | INDICATED ON THE SURVEY COMPLYING WITH |
| | NFPA 58, PLEASE ADD THE MEASUREMENTS FOR |
| | THE RESUBMITTAL. |
| | 6. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. PLEASE DO |
| | THIS PRIOR TO RESUBMITTING. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |
| | |
| | |
| | |
| | |