Plan Review Notes
Plan Review Notes For Permit 06071649
Permit Number 06071649
Review Stop G
Sequence Number 2
Notes
Date Text
2006-09-15 00:00:00******DENIED 2ND TIME*****
  
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED FOR GAS PLAN REVIEW DUE TO THE
 FACT THAT THE PREVIOUS COMMENTS HAVE NOT
 BEEN ADDRESSED:
  
 1. MORE INFOMATION IS REQUIRED ON THE
 TYPE OF MATERIAL THAT IS BEING INDICATED
 ON THE GAS RISER DIAGRAM. WHAT IS "CTS"?
 PLEASE CLARIFY FOR THE RESUBMITTAL.
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: PLEASE INDICATE THE BTU LOAD LOAD
 OF THE GENERATOR ON THE ISOMETRIC RISER
 DIAGRAM FOR THE RESUBMITTAL.
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 NOTE: PLEASE SUBMIT MANUFACTURER CUT
 SHEETS OF THE 1ST AND 2ND STAGE
 REGULATORS.
 4.PLEASE INDICATE WHICH MODEL GENERATOR
 IS BEING USED IN THE MANUFACTURER
 ISTALLATION AND OWNERS MANUAL ON PAGE 6
 SO THAT THE GENERATOR BTU LOADS CAN BE
 VERIFIED.
 5. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 NOTE: THERE ARE NO MEASUREMENTS
 INDICATED ON THE SURVEY COMPLYING WITH
 NFPA 58, PLEASE ADD THE MEASUREMENTS FOR
 THE RESUBMITTAL.
 6. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved