| 2006-09-14 00:00:00 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | THE VALUE ON THE APPLICATION MUST |
| | INCLUDE THE TOTAL COST OF LABOR AND |
| | MATERIAL FOR THE GENERATOR, EQUIPMENT |
| | (TRANSFER SWITCHES, PANELS ETC.) |
| | AND PAD PER 108.3 FBC AS AMENDED. |
| | INCREASE THE VALUE AT THE COUNTER WHEN |
| | RESUBMITTING, AND GET A RECEIPT FROM THE |
| | PERMIT CLERK.VALUE HAS BEEN INCREASED BY |
| | REVIEWER, FEE MUST BE PAID PRIOR TO RE |
| | SUBMITTING FOR REVIEW. |
| | |
| | |
| | 1} THE RISER DIAGRAM IS NOT LEGIBLE. |
| | PLEASE INCREASE THE SIZE OR REDRAW FOR |
| | CLARITY. 106.1.3 FBC AMMENDED. STILL NOT |
| | LEGIBLE ENOUGH TO RETAIN FOR RECORDS. |
| | |
| | 2} PLEASE NOTE A DISCONNECT IS REQUIRED |
| | PER 225.31 AND 32. INDICATE LOCATION ON |
| | THE RISER AND SITE PLAN. THE TRANSFER |
| | SWITCH MAY NOT MEET THIS REQUIREMENT, |
| | SEE SPECS BEFORE SUBMITTING. CAN'T READ |
| | RISER. UTILITY CONNECTION NOT INDICATED. |
| | IS THE TRANSFER SWITCH NOW THE FIRST |
| | MEANS OF DISCONNECT? |
| | |
| | 3} PROVIDE A SITE DIAGRAM PER 106.3.5.4 |
| | FBC AS AMMENDED, INCLUDING GENERATOR AND |
| | RELATED EQUIPMENT AND ALL SERVICE |
| | EQUIPMENT. SURVEY IS NOT A SITE PLAN. |
| | ALL EQUIPMENT WAS NOT LISTED ON THE |
| | "SURVEY" EITHER. |
| | |
| | 5} PROVIDE SPECIFICATIONS FOR THE |
| | TRANSFER SWITCH, INDICATING NUMBER OF |
| | POLES, AND HOW BOTH GENERATOR AND |
| | UTILITY POWER SOURCE CAN BE |
| | DISCONNECTED.THE SPECIFICATIONS PROVIDED |
| | DO NOT ALLOW FOR THE UTILITY TO BE |
| | DISCONNECTED. |
| | |