2006-09-14 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 THE VALUE ON THE APPLICATION MUST
 INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL FOR THE GENERATOR, EQUIPMENT
 (TRANSFER SWITCHES, PANELS ETC.)
 AND PAD PER 108.3 FBC AS AMENDED.
 INCREASE THE VALUE AT THE COUNTER WHEN
 RESUBMITTING, AND GET A RECEIPT FROM THE
 PERMIT CLERK.VALUE HAS BEEN INCREASED BY
 REVIEWER, FEE MUST BE PAID PRIOR TO RE
 SUBMITTING FOR REVIEW.
  
  
 1} THE RISER DIAGRAM IS NOT LEGIBLE.
 PLEASE INCREASE THE SIZE OR REDRAW FOR
 CLARITY. 106.1.3 FBC AMMENDED. STILL NOT
 LEGIBLE ENOUGH TO RETAIN FOR RECORDS.
  
 2} PLEASE NOTE A DISCONNECT IS REQUIRED
 PER 225.31 AND 32. INDICATE LOCATION ON
 THE RISER AND SITE PLAN. THE TRANSFER
 SWITCH MAY NOT MEET THIS REQUIREMENT,
 SEE SPECS BEFORE SUBMITTING. CAN'T READ
 RISER. UTILITY CONNECTION NOT INDICATED.
 IS THE TRANSFER SWITCH NOW THE FIRST
 MEANS OF DISCONNECT?
  
 3} PROVIDE A SITE DIAGRAM PER 106.3.5.4
 FBC AS AMMENDED, INCLUDING GENERATOR AND
 RELATED EQUIPMENT AND ALL SERVICE
 EQUIPMENT. SURVEY IS NOT A SITE PLAN.
 ALL EQUIPMENT WAS NOT LISTED ON THE
 "SURVEY" EITHER.
  
 5} PROVIDE SPECIFICATIONS FOR THE
 TRANSFER SWITCH, INDICATING NUMBER OF
 POLES, AND HOW BOTH GENERATOR AND
 UTILITY POWER SOURCE CAN BE
 DISCONNECTED.THE SPECIFICATIONS PROVIDED
 DO NOT ALLOW FOR THE UTILITY TO BE
 DISCONNECTED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  