Plan Review Notes
Plan Review Notes For Permit 06071649
Permit Number 06071649
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-09 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 THE VALUE ON THE APPLICATION MUST
 INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL FOR THE GENERATOR, EQUIPMENT
 (TRANSFER SWITCHES, PANELS ETC.)
 AND PAD PER 108.3 FBC AS AMENDED.
 INCREASE THE VALUE AT THE COUNTER WHEN
 RESUBMITTING, AND GET A RECEIPT FROM THE
 PERMIT CLERK.
  
  
 1} THE RISER DIAGRAM IS NOT LEGIBLE.
 PLEASE INCREASE THE SIZE OR REDRAW FOR
 CLARITY. 106.1.3 FBC AMMENDED.
  
 2} PLEASE NOTE A DISCONNECT IS REQUIRED
 PER 225.31 AND 32. INDICATE LOCATION ON
 THE RISER AND SITE PLAN. THE TRANSFER
 SWITCH MAY NOT MEET THIS REQUIREMENT,
 SEE SPECS BEFORE SUBMITTING.
  
 3} PROVIDE A SITE DIAGRAM PER 106.3.5.4
 FBC AS AMMENDED, INCLUDING GENERATOR AND
 RELATED EQUIPMENT AND ALL SERVICE
 EQUIPMENT.
  
 4} INDICATE WHICH MODEL GENERATOR IS
 BEING USED, THE SPEC BOOK IS GENERIC.
  
 5} PROVIDE SPECIFICATIONS FOR THE
 TRANSFER SWITCH, INDICATING NUMBER OF
 POLES, AND HOW BOTH GENERATOR AND
 UTILITY POWER SOURCE CAN BE
 DISCONNECTED.
  
 6} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW