| 2006-08-03 00:00:00 | ******DENIED****** |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR GAS PLAN REVIEW: |
| | |
| | 1. A GAS PERMIT CAN NOT BE ISSUED UNTIL |
| | A GEN/RES PERMIT APPLICATION HAS BEEN |
| | APPLIED FOR AND APPROVED BY ZONING FOR |
| | THE GENERATOR LOCATION. |
| | 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. PLEASE REFERENCE |
| | ISOMETRIC EXAMPLE IN RED INK. |
| | 3. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED AND ALL PIPE SIZES. PLEASE |
| | REFERENCE ISOMETRIC EXAMPLE IN RED INK. |
| | 4. INDICATE GENERATOR DIMENSIONS ON SITE |
| | SURVEY FROM PROPERTY LINES AND DISTANCES |
| | FROM ADJACENT DWELLING STRUCTURES. |
| | 5. PLEASE CORRELATE PIPE SIZES ON SITE |
| | SURVEY, ONE INDICATES 1-1/2" THE OTHER |
| | INDICATES 1"1/2. THE ISOMETRIC DRAWING |
| | INDICATES 1/2". |
| | 6. PLEASE REFERENCE THE EXAMPLE |
| | ISOMETRIC DRAWING FOR RESUBMITTAL, THE |
| | ISOMETRIC DRAWING THAT WAS SUBMITTED |
| | DOES NOT REFLECT THE SITE SURVEY AND IS |
| | NOT AN ISOMETRIC DRAWING. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. ONLY ONE CORRECTED DRAWING AND |
| | ISOMETRIC EXAMPLE IN RED INK FOR |
| | REFERENCE FOR RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |
| | |
| | |
| | |