| Plan Review Notes For Permit 06071634 |
| Permit Number |
06071634 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-11-20 14:50:27 | ****** PROVISO ******** | | | | | | 1) NOTE: PLEASE SEE 310.15B6 FOR THE MINIMUM SIZE FOR | | | THE FEEDER CONDUCTORS FOR NEW 125A PANEL FROM THE 125A | | | BREAKER LOCATED IN NEW 200A METER/MAIN COMBO PANEL. | | | THE #3'S AS SHOWN ON PANEL SCHEDULE ARE NOT LARGE | | | ENOUGH. | | | PLEASE SEE RISER SHOWS 3-3/0'S WHICH ARE WELL OVER THE | | | MINIMUM REQUIRED. THE 3/0'S ARE PERMITTED, HOWEVER WILL | | | MOST LIKELY NOT FIT INTO A 125A BREAKER. | | | | | | | | | *** PLEASE CORRELATE AND ADJUST THE ABOVE BEFORE ANY | | | ROUGH/SLAB INSPECTION. | | | "THIS WILL BE REQUIRED BEFORE THE INSPECTION FOR THE | | | REQUIRED FOOTER STEEL CONNECTION" | | | | | | ** IF PLANS COME BACK FOR ANY REASON WITH COMMENTS FROM | | | ANY OF THE OTHER TRADES, PLEASE ADDRESS AT THIS TIME. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN | | | CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|