2006-09-23 00:00:00DENIED,
 1. THE PROPOSED A/C UNIT CANNOT BE
 LOCATED AT THE SIDE SETBACK.
 2. SURVEY SHOWS THE SIDE SETBACK AT 4.81
 AND SITEPLANS SHOWS 5FT. SURVEY IS A
 LEGAL DOCUMENT, NEED TO RE-LOCATE THE
 PROPOSED A/C UNIT.
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
 A/C UNIT WILL BE ON PROPERTY LINE.
 3. THE SITEPLANS DOES NOT SHOW THE
 SETBACKS OF THE EXISTING PROPERTY FRONT
 & SIDE.
 4. PLEASE USE THE SURVEY (LEGAL
 DOCUMENT) TO SHOW THE PROPOSED ADDITION
 WITH SETBACKS AND SHOW THE LOCATION OF
 THE A/C UNIT. (2 COPIES OF SURVEYS)
  