| 2006-10-01 00:00:00 | **** UNSAT 2ND REVIEW *** |
| | |
| | ** PLEASE SEE SOME FROM PREVIOUS REVIEW |
| | AND SOME NEW NOTES. |
| | NOTES BELOW ARE TAKEN DIRECLTY FROM |
| | PREVIOUS REVIEW WITH NEW NOTES ADDED. |
| | |
| | 1) NOTE: OK. |
| | |
| | 2) NOTE: OK, 22K SHOWN. |
| | |
| | 3) NOTE: NO, SERVICE IS NOT CLEAR. |
| | PLEASE SEE A NEW SERVICE IS BEING |
| | INSTALLED ON ADDTION WHICH IS OK, |
| | HOWEVER THERE IS A 150A BREAKER BEING |
| | NOTED, HOWEVER THIS DOES NOT INDICATE |
| | WHERE THIS IS GOING. PLEASE ALSO SEE THE |
| | EXISTIGN METER/MAIN PANEL LOCATION IS |
| | BEING NOTED AS BEING CHANGED TO A |
| | "J-BOX"?? PLEASE CLARIFY THIS . IS THERE |
| | ANOTHER SUB FEED TO AND PANEL SOMEWHERE |
| | ELSE? AS PLANS ONLY SHOW THIS AS A |
| | 'J-BOX" HOW ARE ALL THE EXISTIGN |
| | CIRCUITS BEING FED? IF THIS EXISTING |
| | PANEL IS WP RATED, W/OUT THE METER BEING |
| | INSTALLED THEN THE PLEASE INDICATE, AS |
| | WELL ASFEEDERS ALONG WITH SHOWING THE |
| | CONDUCTORS, AS COUNDUIT ONLY MENTIONS 2" |
| | WITH #6 GROUND?? |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PANEL NOTES MENTIONS |
| | THIS IS AN EXISTING SERVICE YET PLANS |
| | AND RISER SHOWS THIS AS NEW> PLEASE |
| | CORRELATE AND PLACE ON PLANS WHAT THIS |
| | IS? |
| | PLEASE ALSO SEE LOCATION OF ALL SERVICE |
| | EQUIPMENT SHOULD BE SHOWN. |
| | PLEASE SEE TWO AREAS OF PLANS WHERE |
| | PANELS SEEM TO BE DRAWN. PLEASE SEE SEE |
| | IF NOTE MENTIONS THIS IS EXISTING, IT IS |
| | UNCLEAR HOW THIS IS POSSIBLE WHEN ONE |
| | LOCATION ON PLANS HAS NOT BEENBUILT |
| | YET?? |
| | 240.4, 110.26, UNABLE TO VERIFY AT THIS |
| | TIME. |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 4) NOTE: OK, ALL SD'S ARE NOW SHOWN. |
| | |
| | |
| | 5) NOTE: OK, HOWEVER PLEASE SEE CIRCUIT |
| | WHICH SHOWS 1.92 LOAD ON A #14/15A |
| | CIRCUIT. PLEASE SEE THE MAX KVA ONA 15A |
| | NCIRCUIT IS 1440VA. PLEASE ADJUST. |
| | THE NEW AF CIRCUITS ARE NOTED . |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SPECIFY THE NEW GENERAL |
| | LIGHTING CIRCUIT AS THE CIRCUITS IN |
| | BEDRMS WHERE THIS ADDITION IS BEING |
| | BUILT REQUIRES ARC FAULT FOR |
| | ALL,INCLUDING LTS, RECEPTS, FANS, SD'S |
| | ETC. |
| | PLEASE SEE ONLY CIRUITS OUTSIDE THE |
| | BEDRM UNDER THE CURRENT NEC 2002 DO NOT |
| | REQUIRE THIS. |
| | 210.12B, 408.4 |
| | |
| | 6) NOTE: NO, PLEASE SEE NOTE ## ABOVE AS |
| | THESE ARE ABOUT THE SAME NOTE. |
| | |
| | ** PREVIOUS REVIE WNOTE ** |
| | PLEASE VERIFY THE NEW "J-BOX" |
| | WITH WHAT IS BEING SHOWN WITH A 2" |
| | CONDUIT AND #4. WHAT IS THIS FOR? |
| | |
| | |
| | ******** NEW NOTE ********** |
| | |
| | 7) NOTE: PLEASE SEE PREVIOUS PLANS CAME |
| | IN BEING SIGNED AND SEALED BY AN |
| | ENGINEER, HOWEVER THESE PLANS ARE NOW |
| | COMING BACK WITHOUT ANYTHING?? |
| | PLEASE KNOW, UNDER FS 481.229, THE PLANS |
| | FOR THE ELECTRICLA , PLUMB, MECH AND |
| | ELECTRICAL DO "NOT" HAVE TO BE SIGNED |
| | AND SEALED BY AN ENGINEER OR ARCHITECT |
| | WHEN IT COMES TO A SF RESIDENCE. THESE |
| | MAY BE DONE BY THE CONTRACTOR/OR THE O/B |
| | IN THIS CASE. PLEASE DO KNOW HOWEVER THE |
| | PLANS ARE REQUIRED TO CONTAIN THE |
| | PRINTED NAME AND THE SIGNATURE OF THE |
| | PERSON TAKING RESPONSIBILTY OF SAID |
| | PLANS. |
| | FS 481.229, |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 8) NOTE: PLEASE SEE MISSING RECEPT W/IN |
| | 6' OF REAR DOOR INSIDE, REDLINED ON ONE |
| | SET.210.52 |
| | |
| | ** PLEASE CALL TO GO OVER THE SCENARIO |
| | OF THE SERVICE. |
| | |
| | |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |