| Date |
Text |
| 2006-08-09 00:00:00 | *** UNSAT *** |
| | |
| | |
| | 1) NOTE: PLEASE SEE NOTE #7 WHICH IS |
| | STATING A CODE NOT FROM THE 2002 NEC. IN |
| | FACT IT APPEARS TO BE FROM THE 1996 NEC. |
| | PLEASE ADJUST. |
| | |
| | 2) NOTE: PLEASE VERIFY WITH FPL THE |
| | AVAILABLE FAULT CURRENT AND THEN PLANS |
| | CORRELATE THAT RATING WITH EQUIPMENT ON |
| | PLANS. PLEASE SEE PLANS NOTE TWO |
| | SEPARATE AIC RATINGS. |
| | PLEASE SEE 110.9. |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 3) NOTE: PLEASE SEE PANEL NOTES MENTIONS |
| | THIS IS AN EXISTING SERVICE YET PLANS |
| | AND RISER SHOWS THIS AS NEW> PLEASE |
| | CORRELATE AND PLACE ON PLANS WHAT THIS |
| | IS? |
| | PLEASE ALSO SEE LOCATION OF ALL SERVICE |
| | EQUIPMENT SHOULD BE SHOWN. |
| | PLEASE SEE TWO AREAS OF PLANS WHERE |
| | PANELS SEEM TO BE DRAWN. PLEASE SEE SEE |
| | IF NOTE MENTIONS THIS IS EXISTING, IT IS |
| | UNCLEAR HOW THIS IS POSSIBLE WHEN ONE |
| | LOCATION ON PLANS HAS NOT BEENBUILT |
| | YET?? |
| | 240.4, 110.26, UNABLE TO VERIFY AT THIS |
| | TIME. |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 4) NOTE: PLEASE NOTE ABOVE ON LANS |
| | MENTIONS THE REQUIEMENT FOR SD'S IN |
| | EXISTING DWELLING, YET THE EXISTING |
| | DWELLING LAYOUT IS NOT SHOWN SHOWING |
| | SD'S INSIDE AND OUTSIDE THE EXISTING |
| | BEDRMS. |
| | R313, FBC 2004 NFPA-72 11.5.1.1, 11.8.3 |
| | |
| | 5) NOTE: PLEASE SPECIFY THE NEW GENERAL |
| | LIGHTING CIRCUIT AS THE CIRCUITS IN |
| | BEDRMS WHERE THIS ADDITION IS BEING |
| | BUILT REQUIRES ARC FAULT FOR |
| | ALL,INCLUDING LTS, RECEPTS, FANS, SD'S |
| | ETC. |
| | PLEASE SEE ONLY CIRUITS OUTSIDE THE |
| | BEDRM UNDER THE CURRENT NEC 2002 DO NOT |
| | REQUIRE THIS. |
| | 210.12B, 408.4 |
| | |
| | 6) NOTE: PLEASE VERIFY THE NEW "J-BOX" |
| | WITH WHAT IS BEING SHOWN WITH A 2" |
| | CONDUIT AND #4. WHAT IS THIS FOR? |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |