Plan Review Notes
Plan Review Notes For Permit 06071634
Permit Number 06071634
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-09 00:00:00*** UNSAT ***
  
  
 1) NOTE: PLEASE SEE NOTE #7 WHICH IS
 STATING A CODE NOT FROM THE 2002 NEC. IN
 FACT IT APPEARS TO BE FROM THE 1996 NEC.
 PLEASE ADJUST.
  
 2) NOTE: PLEASE VERIFY WITH FPL THE
 AVAILABLE FAULT CURRENT AND THEN PLANS
 CORRELATE THAT RATING WITH EQUIPMENT ON
 PLANS. PLEASE SEE PLANS NOTE TWO
 SEPARATE AIC RATINGS.
 PLEASE SEE 110.9.
 FBC 106.1.2 ADMIN SECT.
  
 3) NOTE: PLEASE SEE PANEL NOTES MENTIONS
 THIS IS AN EXISTING SERVICE YET PLANS
 AND RISER SHOWS THIS AS NEW> PLEASE
 CORRELATE AND PLACE ON PLANS WHAT THIS
 IS?
 PLEASE ALSO SEE LOCATION OF ALL SERVICE
 EQUIPMENT SHOULD BE SHOWN.
 PLEASE SEE TWO AREAS OF PLANS WHERE
 PANELS SEEM TO BE DRAWN. PLEASE SEE SEE
 IF NOTE MENTIONS THIS IS EXISTING, IT IS
 UNCLEAR HOW THIS IS POSSIBLE WHEN ONE
 LOCATION ON PLANS HAS NOT BEENBUILT
 YET??
 240.4, 110.26, UNABLE TO VERIFY AT THIS
 TIME.
 FBC 106.1.2 ADMIN SECT.
  
 4) NOTE: PLEASE NOTE ABOVE ON LANS
 MENTIONS THE REQUIEMENT FOR SD'S IN
 EXISTING DWELLING, YET THE EXISTING
 DWELLING LAYOUT IS NOT SHOWN SHOWING
 SD'S INSIDE AND OUTSIDE THE EXISTING
 BEDRMS.
 R313, FBC 2004 NFPA-72 11.5.1.1, 11.8.3
  
 5) NOTE: PLEASE SPECIFY THE NEW GENERAL
 LIGHTING CIRCUIT AS THE CIRCUITS IN
 BEDRMS WHERE THIS ADDITION IS BEING
 BUILT REQUIRES ARC FAULT FOR
 ALL,INCLUDING LTS, RECEPTS, FANS, SD'S
 ETC.
 PLEASE SEE ONLY CIRUITS OUTSIDE THE
 BEDRM UNDER THE CURRENT NEC 2002 DO NOT
 REQUIRE THIS.
 210.12B, 408.4
  
 6) NOTE: PLEASE VERIFY THE NEW "J-BOX"
 WITH WHAT IS BEING SHOWN WITH A 2"
 CONDUIT AND #4. WHAT IS THIS FOR?
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  