| Plan Review Notes For Permit 06071631 |
| Permit Number |
06071631 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-03-02 18:20:28 | *** UNSAT ** | | | | | | 1) NOTE: PLEASE SEE PREVIOUS NOTES. PLEASE PROVIDE | | | MINIMUM LIGHTING LEVELS PER LIFE SAFETY CODE. NFPA-101 | | | 7.8.1.3, 7.9.2.2. | | | LIGHTING FOR CONTROL OF LIGHTS TO BE AT THE UPPER | | | LOCATION OF STAIRS FOR EGRESS AND LOWER PORTION OF | | | STAIRS. | | | | | | 2) NOTE: PLEASE SEE 13-415.1.1, .1.2, AND .1.3 | | | AUTOMATIC LIGHTING CONTROL SHUT OFF FOR NEW UPSTAIRS | | | AREA REQUIRED. | | | THIS IS A NEW NOTE AND CONFIRMED WITH THE STATE. | | | | | | ** NOTE # 2 COULD BE REDLINED ON PLANS WITH REVISION TO | | | FOLLOW, HOWEVER PLEASE SEE NOTE #1 IS MINIMUM NEEDED | | | FOR LIFE SAFETY. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|