2006-11-16 11:51:32*** UNSAT ***
  
 1) NOTE: PLEASE SUBMIT A PLAN/DETAIL FOR THE REQUIRED
 LIGHTING UNDER NORMAL AND EMERGENCY FOR NEW STORAGE
 AREA EGRESS. THE SHEETS AS SUBMITTED DO NOT COMPLY AND
 DO NOT PROVIDE ENOUGH INFORMATION FOR THE SAGE LIGHTING
 ILLUMINATION OF THESE NEW STAIRS AS SHOWN.
 PLEASE ALSO ONLY SUBMIT PLANS, AND INFORMATION FOR NEW
 AREA AND STAIRS.
  
 THIS IS REQUIRED AT THIS TIME.
 FBC ADMIN SECT(S) 106.1.2, 106.3.5.1.2,AND LIFE
 SAFETY CODE 101 2003, 7.8.1.3, 7.9.2.2.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. *
 *IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF THE
 NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE DO
 NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  