Plan Review Notes
Plan Review Notes For Permit 06071512
Permit Number 06071512
Review Stop E
Sequence Number 5
Notes
Date Text
2006-11-14 10:51:12**** NOTES REDLINED *****
  
 ** NEW ENGINEER OF RECORD.
  
 **CANALES AND ASSOCIATES AND LUIS LOPEZ ARE NOT ON THE
 TITLE BLOCKS FOR THE ELECTRICAL PLANS.
  
  
 1) NOTE: PLEASE WASHER/LAUNDRY LOAD SHOWN AS 1.2 ON
 PANEL SCHEDULE AND LOAD CALCULATIONS WHERE CODE
 210.11C2 AND 220.16 REQUIRES A MINIMUM OF 1.5.
 PLEASE SEE NOTE ON PANEL SCHEDULE WHICH ALSO MENTIONS
 LAUNDRY LOAD OF 1.5 FIGURED IN WITH SMALL APPLIANCE
 LOAD?
  
 2) NOTE: PLEASE SEE PANEL IS BEING SHOWN AS 200A?S WITH
 A 100A FEED. THIS IS TO BE VERIFIED IN FIELD AND
 CORRELATE/ADJUST ON PLANS IF NEEDED.
  
 3) NOTE: REDLINED CODES RELEVANT TO DESIGN WHICH SHOULD
 BE STATED ON PLANS.
 2002 NFPA-72, 2002 NFPA-70 (NEC).
  
  
 PLANS ARE BEING ROUTED BACK TO LUIS MARTINEZ AS THE
 VALUE WAS NOT ADJUSTED BASED ON THE PREVIOUS BUILDING
 REVIEWER?S COMMENTS. IF VALUE IS NOT BEING ADJUSTED,
 THE NEW BUILDING REVIEWER OF RECORD SHALL PROCESS PLANS
 FOR ISSUANCE.
  
  
  
  
  