| Plan Review Notes For Permit 06071512 |
| Permit Number |
06071512 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2006-11-14 10:51:12 | **** NOTES REDLINED ***** | | | | | | ** NEW ENGINEER OF RECORD. | | | | | | **CANALES AND ASSOCIATES AND LUIS LOPEZ ARE NOT ON THE | | | TITLE BLOCKS FOR THE ELECTRICAL PLANS. | | | | | | | | | 1) NOTE: PLEASE WASHER/LAUNDRY LOAD SHOWN AS 1.2 ON | | | PANEL SCHEDULE AND LOAD CALCULATIONS WHERE CODE | | | 210.11C2 AND 220.16 REQUIRES A MINIMUM OF 1.5. | | | PLEASE SEE NOTE ON PANEL SCHEDULE WHICH ALSO MENTIONS | | | LAUNDRY LOAD OF 1.5 FIGURED IN WITH SMALL APPLIANCE | | | LOAD? | | | | | | 2) NOTE: PLEASE SEE PANEL IS BEING SHOWN AS 200A?S WITH | | | A 100A FEED. THIS IS TO BE VERIFIED IN FIELD AND | | | CORRELATE/ADJUST ON PLANS IF NEEDED. | | | | | | 3) NOTE: REDLINED CODES RELEVANT TO DESIGN WHICH SHOULD | | | BE STATED ON PLANS. | | | 2002 NFPA-72, 2002 NFPA-70 (NEC). | | | | | | | | | PLANS ARE BEING ROUTED BACK TO LUIS MARTINEZ AS THE | | | VALUE WAS NOT ADJUSTED BASED ON THE PREVIOUS BUILDING | | | REVIEWER?S COMMENTS. IF VALUE IS NOT BEING ADJUSTED, | | | THE NEW BUILDING REVIEWER OF RECORD SHALL PROCESS PLANS | | | FOR ISSUANCE. | | | | | | | | | | | | | | | |
|