Plan Review Notes
Plan Review Notes For Permit 06071512
Permit Number 06071512
Review Stop E
Sequence Number 4
Notes
Date Text
2006-10-22 10:32:18******** UNSAT 4THREVIEW ******
  
 *** PLEASE SEE NOTES FROM PREVIOUS REVIEWSWHICH STILL
 NEED TO BE ADDRESSED AND PLANS TO BE SUBMITTED TO THE
 2002 NEC. NFPA-70.
  
 ** PLEASE ALSO SEE NEW NOTES DUE TO CHANGES IN PLANS.
  
  
 1) NOTE: PLEASE SEE PLANS STILL NOT INIDCATE ALL
 CIRCUITING AND CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULES.
 PLEASE SEE THERE ARE STILL MANY DEVICES FOR WHAT IS
 DEDICATE D EQUIPMENT ETC WHICH IS NOT ON PANEL
 SCHEDULE. PLEASE SEE THE FOLLOWING.
  
 A) HALLWAY FOYER SHOWS UCFRIG, ICE MACHINE, COUNTER
 RECEPTS ETC WITH OUT ANY CIRCUITS.
 B) PLEASE SEE SPACES ON PANEL SCHEDULE SHOWING CIRCUITS
 HOWEVER NOT LOCATED ON PLANS?
 C) PLEASE SEE PLANS WHICH SHOWS CIRCUITS , 8, 10 ETC
 WHICH ARE SHOWN AS BLANK ON PANEL SCHEDULE??
 D) PLEASE SEE MISSING CIRCUITS ON OTHER DEVICES.
 ETC ETC.
 240.4,220.31,310.16, ETC
 FBC 106.1.2, 106.1.3, 106.3.5.1.2 ADMINISTRATIVE
 SECTIONS.
  
 2) NOTE: PLEASE SEE KITCHEN COUNTER SPACE MISSING GFI
 RECEPT AS REQUIRED AS A DEDICATED MICROWAVE CIRCUIT IS
 NOW SHOWN (#4) , HOWEVER NO THER RECEPT (GF) IS SHOWN
 ?
 PLEASE SEE 210.52C1, 220.16, 210.11C1, 210.8A6,
  
 3) NOTE: PLEASE SEE 250.52B1, 210.11C1,220.16 AS
 CIRCUIT, LOAD ETC FOR KITCHEN, DINING, AND AREAS OF THE
 LIKE ARE NOT COMPLIANT ON PLANS. (#21)
 PLEASE ALSO SEE RECEPT IN SMAE LOCATION MISSING
 CIRCUITING AS NOTED ABOVE IN NOTE #1.
  
 4) NOTE: PLEASE SEE PANEL SCHEDULE AND LOAD
 CALCULATIONS DO NOT CORRELATE. THERE ARE LOADS ON PANEL
 SCHEDULE WHICH IS NOT IN CACULATIONS. PLEASE SEE OTHER
 CIRCUITS REQUIRED FOR DEDICATED EQUIPMENT AS NOTED
 ABOVE ARE ALSO NOT ON PANEL SCHEDULE OR IN LOAD
 CALCULATIONS, HOWEVER SHOWN ON PLANS??
 PLEASE SEE PREVIOUS PLANS FROM THE PREVIOUS 3 SUBMITTED
 SETS ALL INDICATED A 200A PANEL EXISTING. PLEASE SEE
 THIS PANEL IS BEING SHOWN AS 100A AND LOAD IS BEING
 SHOWN AT 100A'S ALREADY WITHOUT ANY OF THE OTHER ITEMS
 ON PANEL BEING FIGURED INTO THE LOAD CALCULATIONS.
 PLEASE KNOW, BASED ON THE PLANS, LOADS, CIRCUITS AND
 THE DEDICATED CIRCUITS NOT SHOWN, THE 100A PANEL IS
 OVERLOADED AND W3ILL BE REQUIRED TO BE UPGRADED FOR
 ADDTIONAL SERVICE LOADS.
 PLEASE ADJUST ALL; , SUBMIT NEW RISER, FOR NEW FEEDERS,
 UPDATE LOAD CALCULATIONS, SIZE OF THE OCP FEEDING NEW
 PANEL UPGRADE ETC ETC.
 PLEASE SEE NEC 2002,
 220.31, 408.4, 240.4, 310.16, 300, 230,ETC ETC.
 THERE ARE MANY ARTICLES IN THE NEC WHICH APPLY HOWEVER
 ALL ARTICLES WILL NOT BE LISTED.
  
 5) NOTE: PLEASE KNOW, AS CONSULATATION WITH THE STATE
 INVESTIGATOR FOR THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS HAS ALREADY TAKEN PLACE. PLEASE KNOW AS
 "CANALES AND ASSC'S" IS NOT LEGALLY EMPLOYED BY THE
 SAID ENGINEERSIGNING AND SEALING DOCUMENTS AND DO NOT
 MEET THE EXCEPTIONS UNDER FS 481.229 (1)(C, PLEASE BE
 SURE ANY NEW PLANS SUBMITTED ARE DONE LICENSED
 PROFESSIONALS WHICH ARE PERMITTED TO DO THE SCOPE OF
 WORK AS SHOWN.
 PLEASE KNOW ALL PREVIOUS PLANS WHICH WERE SIGNED DATED
 AND SEALED BY MR. LUIS LOPEZ HAVE BEEN RETAINED FOR
 THIS PROJECT WILL BE TURNED OVER TO THE BOARD OF
 ENGINEERS FOR REVIEW.
 PLEASEKNOW A 4XFEE HAS ONCE AGAIN BEEN ASSESSED AS
 REQUIRED PER FS 553.80(2)(B). THIS NOTICE WAS GIVEN ON
 ALL PREVIOUS REVIEWS AND A 4X FEE WAS ALREADY ASSESSED
 ON PREVIOUS REVIEW.AS REQUIRED UDNER FLORIDA STATUE
 AS NOTED, THIS FEE IS ASSESSED EACH TIME AFTER.
 PLEASE KNOW,ONE SET OF ALL PLANS, INCLUDING BUILDING,
 PLUMBING ETC WILL BE RETAINED BY THIS OFFICE AND SHALL
 BE FORWARDED WITH PREVIOUS SADI DOCUMENTS.
  
 THE FEE OF $624.00 WILL ONCE AGAIN BE REQUIRED TO BE
 PAID BEFORE RESUBMITTING PLANS.
  
 ****PLEASE KNOW, TO DATE THE DESIGNER OR ENGINEER OF
 RECORDED SHOWN ON SAID PLANS HAS NOT CONTACTED THIS
 REVIEWER FOR ANY QUESTIONS OR COMMENTS.
  
 6) NOTE: NOTICE TO CONTRACTOR, PLEASE KNOW THW RECORDED
 NOTICE OF COMMENCEMENT WILL EXPIRE ON OCT 25TH AS WORK
 HAS NOT COMMENCED WITHIN 90 DAYS OF RECORDING SUCH NOC.
 PLEASE SEE FS 713.13(2) .
 PLEASE ALSO KNOW, THE RE-RECORDED NOC IS ONLY NEEDS TO
 BE SUBMITTED ONCE PERMIT IS ISSUED AND IS BEING PICKED
 UP.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.