Plan Review Notes For Permit 06071512
Permit Number 06071512
Review Stop E
Sequence Number 3
Notes
Date Text
2006-09-24 00:00:00***** UNSAT 3RD REVIEW ******
  
 ** PLEASE SEE PREVIOUS REVIEW NOTE
 REQUESTED TO SUBMIT PLANS FOR 2002 NEC
 CODE COMPLIANCE. PLEASE SEE MANY OF THE
 CODE REFERENCED IN PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED ALONG WITH NEW
 COMMENTS DUE TO THE PLANS SUBMITTED.
 PLEASE SEE NEW COMMENTS FOR NON-CODE
 COMPLIANT ITEMS.
  
 1) NOTE: NO, SAME NOTE.
  
 **PREVIOUS REVIEW NOTE REVIEW #2**
 NO, PREVIOUS REVIEW NOTE #1.
 PLEASE COMPLETE ALL CIRCUITING ON PLANS
 AND CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULE.
 PLEASE SEE PLANS DO NOT INDICATE ANY
 CIRCUITS AND REVIEW FOR CODE COMPLIANCE
 FOR MANY ITEMS CAN NOT BE DONE AT THIS
 TIME.
 PLEASE INDICATE ALL NEW ELECTRICAL AND
 INDICATE ALL EXISTING ELECTRICAL.
 FBC 106.1.2 ADMIN SECT.
 240.4,310.16,408.4 ETC 2002 NEC.
  
 2) NOTE: NO, SAME AS NOW BOTH BATHRMS
 ARE SHOWN ON THE SAME CIRCUIT WHICH IS
 NOT PERMITTED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 PLEASE SEE MISSING RECEPTS
 LOCATED IN BATHRM W/IN 3' OF LAV. PLEASE
 SEE MASTER BATH, EITHER ADD OR RELOCATE
 GFI AS SHOWN. PLEASE SEE OTHER BATH
 WHERE NO GFI IS SHOWN? (NEW OR EXSIT)?
 210.52D
 PLEASE SEE MISSING THE REQUIRED
 DEDICATED BATH CIRCUIT(S) PER 210.11C3
 MUST BE 20A AND #12. SHOWN AS 15A ON
 SCHEDULE.
  
 3) NOTE:??OK. TANKLESS WH REMOVED FROM
 PLANS?
  
  
 4) NOTE:NO, PLEASE SEE DRYER IS STILL
 BEING SHOWN ON A SINGLE POLE CIRCUIT
 WHEN THIS A 220/240 UNIT.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 PLEASE SEE DRYER IS BEING SHOWN
 ON A 1-P15A ON PANEL SCHEDULE, YET THIS
 UNIT IS SHOWN AS 6KW UNIT ON LOAD
 CALCULATIONS. PLEASE SEE NEC FOR SIZING
 OCP AND AWG.
 240.4, 310.16, 220.18
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE:OK, NOTED ON PLANS HOWEVER THE
 CIRCUTING NOT SHOWN ON PANEL SCHEDULE
 FOR CIRCUITS. PLEASE SEE NEC 210.12, IT
 IS THE PROTECTION FOR THE "BRANCH
 CIRCUIT".
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE REQUIRED
 ARC FAULT PROTECTION REQUIRED FOR ALL
 OUTLETS IN BEDRMS. RECEPTS, SD'S,LTS,
 FANS ETC,
 2002 NEC 210.12
  
 8) NOTE: OK, THE SIZE OF THE UNIT HAS
 CHANGED.
  
 9) NOTE: NO, NOT COMPLETE AS LOADS, AND
 CIRCUTING WITH NOTES ABOVE ARE NOT
 COMPLETE AT THIS TIME. PLEASE SEE LOAD
 AT PANEL SCHEDULE IS BLANK ALSO.
  
 ** PREVIOUS REVIEW NOTE ** PLEASE
 COMPELTE PANEL SCHEDULE
 AS NO CONDUCTOR SIZES ARE BEING SHOWN
 FOR BRANCH CIRCUITS. UNABLE TO VERIFY
 MANY REQUIRED MIN SIZES ATTHIS TIME.
 408.6,240.4,310.16 ETC
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE 210.11C2,220.16 FOR
 MIN KVA TO BE FIGURED FOR WASHER/LAUNDRY
 CRICUIT.
  
 11) NOTE: NO? PLEASE VERIFY THE PANEL
 FOR THIS AT THIS TIME. PLEASE KNOW THIS
 IS A NEW BUILDING AND THE SIZE AND
 VOLTAGE SHOULD BE READILY AVAILABLE.
 VOLTAGE IS BEING SHOWN 120/240 AND
 100A'S NOW INSTEAD OF THE PREVIOUS PLANS
 WHICH SHOWED 200A 'S>
 THE CONTRACTOR IS NOT TO VERIFY THIS,
 THIS IS REQUIRED TO BE VERIFIED BY THE
 DESIGN PROFESSIONAL AND PLACED ON PLANS.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 PLEASE SEE NOTE ON PLANS
 MENTIONS FOR CONTRACTOR TO VERIFY 200A
 SERVICE AND TO VERIFY THE CALCULATIONS,
 PANEL SCHEDULE ETC.
 PLEASE KNOW, THIS IS THE RESPONSIBILITY
 OF THEDESIGN PROFESSIONALS AT THIS
 TIME OF THE DESIGN PHASE OF PERMITTING.
 ANY REVISIONS DONE TO PROJECT THEN
 BECOMES THE RESPONSIBILITY OF THE
 CONTRACTOR TO NOTIFY THE DESIGN
 PROFESSIONAL OF REVISIONS AND CHANGES.
 PLEASE VERIFY ALL OF THE ABOVE INCLUDING
 THE VERIFICATION OF A 200A SERVICE,
 INCLUDING THE SIZE OF THE FEEDERS COMING
 INTO THE EXSTING PANEL. IT IS UNCLEAR
 EVEN IF A 200A PANEL WAS INSTALLED IF
 THERE ARE INDEED FEEDERS RATED FOR
 200A'S AND THE INCREASED LOADS.
  
 12) NOTE:NO, AS THERE ARE STILL CODE
 COMPLIANT COMMENTS FOR SOME OF THE SAME
 COMMENTS AS MADE ON TWO PREVIOUS
 REVIEWS, A 4X FEE FOR THE PLAN REVIEW
 PORTION OF THE PERMIT FEE HAS NOW BEEN
 ASSESSED. THIS FEE IS ASSESSED TO THE
 DESIGN PROFESSIONAL AND MUST BE PAID
 BEFORE PLANS CAN BE RESUBMITTED. PLEASE
 KNOW, ALL PREVIOUS PLANS AND CURRENT
 PLANS WILL NOW BE FORWARDED TO THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS
 AND THE STATE BOARD'S LEGAL COUNSEL WITH
 ALL OTHER PREVIOUS PLANS IN FILE. PLEASE
 KNOW IT WILL ALSO BE CONFIRMED AS A
 "DESIGN"/ "DRAFTING FIRM" MAY NOT BE
 ABLE TO DESIGN OR DRAW PLANS FOR A
 COMMERCIAL BUILDING. THIS WILL BE
 CONFIRMED AS FS 481.203, 481.223 AND FS
 481.229 DOES NOT PERMIT THESE TYPES OF
 FIRMS TO PRACTICE "ARCHITECTURE" WITHOUT
 THE PROPER LICENSURE.
 THE AMOUNT OF $624.00 IS NOW DUE BEFORE
 PLANS MAY BE RESUBMITTED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 PLEASE SEEFS 553.80(2)(B)
 WITH RESPECT TO DESIGN PROFESSIONALS AND
 REPEAT CODE COMPLIANT COMMENTS.
 PLEASE SEE MANY OF THE COMMENTS WERE
 REPEAT AS CODES AND ITEMS WERE STATED ON
 THE PREVIOUS REVIEW. PLEASE SEE THIS IS
 A NOTICE GIVEN AT THIS TIME.
 ** PLEASE KNOW ONE SET OF ELECTRICAL
 PLANS FROM EACH OF THE PREVIOUS REVIEWS
 ARE BEING RETAINED BY THIS OFFICE FOR
 POSSIBLE REVIEW BY THE FBPE'S.
  
  
 ***** NEW NOTE ***
  
 1) NOTE: PLEASE SEE NOW A FAULT CURRENT
 CALCULATION HAS NOW BEEN SHOWN ON
 PLANS?? PLEASE SEE THIS NOW STATES MIN
 AIC RATINGS FOR ALL EQUIPMENT TO BE 22K.
 PLEASE SEE PANEL IS BEING SHOWN AS 10K.
 PLEASE VERIFY THIS.
 110.9, 90.7
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  