| Date |
Text |
| 2006-09-10 00:00:00 | ***** UNSAT 2ND REVIEW ****** |
| | |
| | ** PLEASE SEE PREVIOUS REVIEW NOTE |
| | REQUESTED TO SUBMIT PLANS FOR 2002 NEC |
| | CODE COMPLIANCE. PLEASE SEE MANY OF THE |
| | CODE REFERENCED IN PREVIOUS REVIEW STILL |
| | NEED TO BE ADDRESSED ALONG WITH NEW |
| | COMMENTS DUE TO THE PLANS SUBMITTED. |
| | PLEASE SEE NEW COMMENTS FOR NON-CODE |
| | COMPLIANT ITEMS. |
| | |
| | 1) NOTE: NO, PREVIOUS REVIEW NOTE #1. |
| | PLEASE COMPLETE ALL CIRCUITING ON PLANS |
| | AND CORRELATE WITH THE SUBMITTED PANEL |
| | SCHEDULE. |
| | PLEASE SEE PLANS DO NOT INDICATE ANY |
| | CIRCUITS AND REVIEW FOR CODE COMPLIANCE |
| | FOR MANY ITEMS CAN NOT BE DONE AT THIS |
| | TIME. |
| | PLEASE INDICATE ALL NEW ELECTRICAL AND |
| | INDICATE ALL EXISTING ELECTRICAL. |
| | FBC 106.1.2 ADMIN SECT. |
| | 240.4,310.16,408.4 ETC 2002 NEC. |
| | |
| | 2) NOTE: PLEASE SEE MISSING RECEPTS |
| | LOCATED IN BATHRM W/IN 3' OF LAV. PLEASE |
| | SEE MASTER BATH, EITHER ADD OR RELOCATE |
| | GFI AS SHOWN. PLEASE SEE OTHER BATH |
| | WHERE NO GFI IS SHOWN? (NEW OR EXSIT)? |
| | 210.52D |
| | PLEASE SEE MISSING THE REQUIRED |
| | DEDICATED BATH CIRCUIT(S) PER 210.11C3 |
| | MUST BE 20A AND #12. SHOWN AS 15A ON |
| | SCHEDULE. |
| | |
| | 3) NOTE: PLEASE SUBMIT MANUFACTURE |
| | SPECS/CUT SHEETS FOR THE TWO NEW |
| | TANKLESS WATER HEATERS BE PORPOSED. |
| | PLEASE BE SURE THE LISTING FROM A NRTL |
| | IS SHOWN. |
| | PLEASE ALSO SEE BOTH OF THESE ON PANEL |
| | SCHEDULE DO NOT INDICATE ANY CONDUCTOR |
| | SIZES OR OCP ?? |
| | 240.4,310.16 408.6 ETC |
| | |
| | 4) NOTE: PLEASE SEE DRYER IS BEING SHOWN |
| | ON A 1-P15A ON PANEL SCHEDULE, YET THIS |
| | UNIT IS SHOWN AS 6KW UNIT ON LOAD |
| | CALCULATIONS. PLEASE SEE NEC FOR SIZING |
| | OCP AND AWG. |
| | 240.4, 310.16, 220.18 |
| | |
| | 5) NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52 FOR WALL SPACE. (EXISTING TO BE |
| | SHOWN) NEW WALLS TO CONTAIN SPACING PER |
| | 210.52 |
| | |
| | 6) NOTE: PLEASE SEE LIBRARY/ ADAPTABLE |
| | SLEEPING ROOM SHALL CONTAIN SD'S INSIDE |
| | AND OUTSIDE IF NOT EXISTING. |
| | PLEASE SEE NFPA-72 11.5.1.1,11.8.3 R313 |
| | 2004 FBC. |
| | |
| | 7) NOTE: PLEASE INDICATE THE REQUIRED |
| | ARC FAULT PROTECTION REQUIRED FOR ALL |
| | OUTLETS IN BEDRMS. RECEPTS, SD'S,LTS, |
| | FANS ETC, |
| | 2002 NEC 210.12 |
| | |
| | 8) NOTE: PLEASE SEE 424.3B AS LOAD CALCS |
| | INDICATE THE HEAT , A/C LOAD AT 10KW, |
| | HOWEVER THE OCP SHOWN IS ONLY AT 40A'S?? |
| | PLEASE SEE MIN SIZING OF THE OCP IS TO |
| | BE 125%.)MIN) |
| | |
| | 9) NOTE: PLEASE COMPELTE PANEL SCHEDULE |
| | AS NO CONDUCTOR SIZES ARE BEING SHOWN |
| | FOR BRNACH CIRCUITS. UNABLE TO VERIFY |
| | MNAY REQUIRED MIN SIZES ATTHIS TIME. |
| | 408.6,240.4,310.16 ETC |
| | FBC 106.1.2 |
| | |
| | 10) NOTE: PLEASE SEE 210.11C2,220.16 FOR |
| | MIN KVA TO BE FIGURED FOR WASHER/LAUNDRY |
| | CRICUIT. |
| | |
| | 11) NOTE: PLEASE SEE NOTE ON PLANS |
| | MENTIONS FOR CONTRACTOR TO VERIFY 200A |
| | SERVICE AND TO VERIFY THE CALCULATIONS, |
| | PANEL SCHEDULE ETC. |
| | PLEASE KNOW, THIS IS THE RESPONSIBILITY |
| | OF THEDESIGN PROFESSIONALS AT THIS |
| | TIME OF THE DESIGN PHASE OF PERMITTING. |
| | ANY REVISIONS DONE TO PROJECT THEN |
| | BECOMES THE RESPONSIBILITY OF THE |
| | CONTRACTOR TO NOTIFY THE DESIGN |
| | PROFESSIONAL OF REVISIONS AND CHANGES. |
| | PLEASE VERIFY ALL OF THE ABOVE INCLUDING |
| | THE VERIFICATION OF A 200A SERVICE, |
| | INCLUDING THE SIZE OF THE FEEDERS COMING |
| | INTO THE EXSTING PANEL. IT IS UNCLEAR |
| | EVEN IF A 200A PANEL WAS INSTALLED IF |
| | THERE ARE INDEED FEEDERS RATED FOR |
| | 200A'S AND THE INCREASED LOADS. |
| | |
| | 12) NOTE: PLEASE SEEFS 553.80(2)(B) |
| | WITH RESPECT TO DESIGN PROFESSIONALS AND |
| | REPEAT CODE COMPLIANT COMMENTS. |
| | PLEASE SEE MANY OF THE COMMENTS WERE |
| | REPEAT AS CODES AND ITEMS WERE STATED ON |
| | THE PREVIOUS REVIEW. PLEASE SEE THIS IS |
| | A NOTICE GIVEN AT THIS TIME. |
| | ** PLEASE KNOW ONE SET OF ELECTRICAL |
| | PLANS FROM EACH OF THE PREVIOUS REVIEWS |
| | ARE BEING RETAINED BY THIS OFFICE FOR |
| | POSSIBLE REVIEW BY THE FBPE'S. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |