| Plan Review Notes For Permit 06071512 |
| Permit Number |
06071512 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-08-18 00:00:00 | *** UNSAT ***** | | | | | | 1) NOTE: PLEASE COMPLETE ALL NEW | | | CIRCUITING ON PLANS AND CORRELATE WITH | | | PANEL SCHEDULE(S) TO BE SUBMITTED. | | | PLEASE SHOW ALL NEW ELECTRICAL ETC. | | | PLEASE CLARIFY RECEPTS (GFI) IN BATH | | | RMS. | | | PLEASE SEE MISSING GFI RECEPTS ALONG | | | KITCHEN COUNTER SPACE. | | | PLEASE SEE MISSING ARC FAULT PROTECTION | | | INDICATED FOR NEW ELECTRICAL IN BEDRMS. | | | 210.8A6,210.12B,210.11C1,210.11C3,408.4, | | | 240.4, 310.16, 210.52D ETC. | | | 2002 NEC. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|