| Plan Review Notes For Permit 06071512 |
| Permit Number |
06071512 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-08-17 00:00:00 | | | | | | | DENIED | | | | | | 1) PROVIDE CONSTRUCTION TYPE ON DRAWING | | | PER 106.3.5 FBC 2004 | | | | | | 2) PROVIDE ALTERATION LEVEL PER 305.1 | | | EXISTING BLDG CODE 2004 | | | | | | 3) SHOWER PAN DETAIL REFERENCES FBC 707 | | | FOR FIRE TREATED WOOD, THIS SECTION IS | | | FOR SHAFT ENCLOSURES, PLEASE CORRECT | | | | | | 4) SOFFIT DETAIL SHALL BE FIRE RETARDANT | | | WOOD PER 603.1 FBC 2004 OR METAL | | | FRAMING, PLEASE INDICATE ON DRAWING | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | |
|