| Plan Review Notes For Permit 06071495 |
| Permit Number |
06071495 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-01-11 15:26:29 | *** REDLINED PLANS*** | | | | | | | | | 1) RISER STILL SHOWS OCP FOR AHU AT 35A, WHERE 424.4B | | | REQUIRES 125% MIN. PLEASE SEE PANEL SCHEDULE SHOWS 50A | | | BREAKER. | | | 2) PLEASE ALSO SEE CODE REQUIRES SMOKE ALARMS.NFPA-72 | | | 11.5.1.1, 11.8.3 |
|