| Date |
Text |
| 2006-07-27 00:00:00 | ******** UNSAT ********* |
| | |
| | 1) NOTE: PLEASE SEE THAT THE FOLLOWING |
| | CODES ARE REFELCTED ON ELECTRICAL PLANS |
| | AT A MINIMUM. NFPA-70 2002 (NEC) AND |
| | NFPA-72 2002. |
| | PLEASE SEE PLANS MENTIONS , "LATEST |
| | EDITIONS", HOWEVER THE LATEST EDITIONS |
| | ARE NOT YET ADOPTED BY THE STATE OF |
| | FLORIDA. |
| | |
| | 2) NOTE: PLEASE BE SURE TITLE BLOCKS |
| | CONTAIN ALL INFORMATION AS REQUIRED BY |
| | FAC 61G1-16.004. PLEASE SEE MISSING THE |
| | PRINTED NAME AND LICENSE NUMEBR OF SAID |
| | ARCHIECT. |
| | PLEASE ALSO BE SURE ALL SEALS ARE |
| | RAISED, CLEAR AND VISSABLE WITH ALL |
| | INFORMATION ON SAID SEALS. PLEASE SEE |
| | THAT MANY OF THE SEALS ARE NOT CELAR. |
| | FS 481.221 |
| | |
| | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9. FBC 106.1.2 |
| | |
| | 4) NOTE: PLEASE CORRELATE AND COMPLETE |
| | INFORMATION FOR AHU KW RATING. PLEASE |
| | SEE LOAD CALCS INDICATE 100% = 6500VA , |
| | YET THE OCP AND CONDUCTOR SIZES LEND TO |
| | THIS AS A 10KW HEAT STRIP? PLEASE |
| | CORRELATE AS THE MECH SHEETS SHOW |
| | ANOTHER SIZE. PLEASE ADJUST ALL ONCE THE |
| | KW RATING IS SET. |
| | 424.3B.,220,310.16,240.4 ETC |
| | |
| | 5) NOTE: PLEASE IDICATE ALL CIRCUITS ON |
| | PANELS WHICH ARE REQUIRED TO CONTAIN ARC |
| | FAULT PROTECTION. PLEASE SEE NOTES FOR |
| | ARC FAULT MENTIONS ONLY RECEPTS, LTS AND |
| | FANS. (NO FANS SHOWN ) ALTHOUGH |
| | PROTECTION OF SD'S IS ALSO REQUIRED. |
| | PELASE SEE NOTE ABOVE MENTIONS AND PLANS |
| | SHOWS SD'S CIRCUITED TO KITCHEN AND BATH |
| | RM LIGHTING, WHICH IS OK, HOWEVER THIS |
| | CIRCUIT WOULD ALSO REQUIRED ARC FAULT |
| | PROTECTION. |
| | 210.12B, 408.4 |
| | |
| | 6) NOTE: PLEASE COMPLETE PANEL SCHEDULE |
| | SPECIFIC TO ALL AREAS. IE LIVING RM |
| | RECEPTS, BATH LTS, BEDRM #3, ETC. |
| | 408.4 |
| | IT IS KNOW TO THIS OFFICE THESE WILL |
| | MOST LIKELY BE REVISED DURING |
| | CONSTRUCTION. |
| | |
| | 7) NOTE: PLEASE SEE A CIRCUIT #17 SEEM |
| | TO BE IN THE CLOSET IN BEDRM #2 WHICH |
| | DOES NOT SEEM TO FEED ANYTHING? |
| | PLEASE CLARIFY. |
| | 106.1.2 |
| | |
| | 8) NOTE: PLEASE SEE MISSING GFI RECEPT |
| | FOR CU. 210.63,210.8A2 |
| | |
| | 9) NOTE: PLEASE SEE MISSING GFI RECEPT |
| | FOR KITCHEN COUNTER SPACE. 210.52C1, |
| | 210.8A6 |
| | |
| | 10) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| | MORE THAN 2' OF WALL SPACE. |
| | 210.52 |
| | *REDLINED** |
| | |
| | 11) NOTE: PLEASE CLARIFY SERVICE. IS |
| | THIS A SEPARATE METER OR A METERMAIN |
| | COMBO? |
| | 106.1.2 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE, PLANS WILL BE |
| | PICKED UP FOR CORRECTIONS. PLEASE KNOW, |
| | BEFORE RESUBMITTING PLANS, ALL |
| | OLD/VOIDED SHEETS MUST BE COMPLETELY |
| | REMOVED FROM SETS AND ONLY NEW REVISED |
| | SHEETS SHOULD BE INSERTED INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. ONLY ONE |
| | COPY OF THE OLD/VOIDED SHEETS SHOULD BE |
| | SUBMITTED SEAPARATELY FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |