| 2006-08-08 00:00:00 | |
| | |
| | DENIED |
| | |
| | 1) THE CLAIMED VALUATION ON THE PERMIT |
| | APPLICATION IS LOW. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT |
| | COST EXCLUDING LAND VALUE. OUR VALUATION |
| | REFERENCE IS ICC (BVD), MARSHALL-SWIFT |
| | AND MEANS COST ANALYSIS SERVICES PER |
| | 108.3 FBC* |
| | |
| | 2) THE STATE OF FLORIDA REQUIRES |
| | COLLECTION OF A RADON SURCHARGE ON ALL |
| | NEW CONSTRUCTION COMPUTED ON UNDER ROOF |
| | FLOOR SPACE PER 10D-91 FAC. THESE FEES |
| | WILL BE ADDED TO THE PERMIT APPLICATION |
| | FEES |
| | |
| | 3) A TITLE BLOCK WITH THE INFORMATION |
| | SPECIFIED PER 61G1-16.004 FAC SHALL BE |
| | PRESENT ON DRAWINGS ISSUED BY THE |
| | RESPONSIBLE ARCHITECT AND MUST,AT A |
| | MINIMUM CONTAIN |
| | 1)FIRM NAME,ADDRESS, AND TELEPHONE # |
| | 2)FIRM LICENCE # |
| | 3)NAME OF PROJECT |
| | 4)DATE PREPARED |
| | 5)A SPACE FOR SIGNATURE & DATED SEAL |
| | 6)A SPACE FOR PRINTED NAME AND LICENCE# |
| | OF PERSON SEALING THE DOCUMENT |
| | |
| | 4) SUBMIT ENGINEERED TRUSS DRAWINGS THAT |
| | COMPLY WITH R802.10.1 FBC WITH PERMIT |
| | APPLICATION OR BEFORE INSTALLATION THAT |
| | HAVE BEEN REVIEWED AND APPROVED BY THE |
| | DESIGNER OF RECORD |
| | |
| | 5) PROVIDE A SITE PLAN THAT SHOWS |
| | DRAINAGE IN COMPLIANCE WITH THE |
| | REQUIREMENTS OF R403.1 |
| | |
| | 6) MINIMUM DESIGN LOADS ON DRAWINGS |
| | REFERENCED TO ASCE 7-98, PLEASE SEE |
| | REFFERENCE ADOPTED BY THE 2004 FBC IS |
| | ASCE 7-02. DRAWINGS TO REFLECT THIS SEE |
| | A/3, A/4 AND A/6 |
| | |
| | 7) GENERAL NOTES A/6 STATE R30 |
| | INSULATION IN CEILING ABOVE CONDITIONED |
| | SPACE BUT WALL SECTION SHOWS R19 PLEASE |
| | CLARIFY |
| | |
| | 8) PROVIDE SILL DETAIL |
| | |
| | 9) DRAWINGS SHOW TOP OF BEAM AT 8'-2" |
| | BUT GARAGE DOOR IS A 7'-0" AND THE |
| | LINTEL PC-1 IS 24" DEEP PLEASE CLARIFY. |
| | |
| | 10) BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SETS OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561) 233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 11) SUBMIT ENERGY CALC'S PER 13-101.2.2 |
| | FBC. BE SURE THAT THEY ARE SIGNED AND |
| | DATED BY PREPARER AND OWNER/AGENT PRIOR |
| | TO SUBMITTAL. PLEASE SUBMIT ON FORM |
| | 600A-2004 AND BE SURE CEILING INSULATION |
| | VALUE MATCHES DRAWINGS |
| | |
| | 12) THE FOLLOWING PRODUCT APPROVALS |
| | REQUIRE CORRECTIONS |
| | A) THURMA-TRU DOES NOT HAVE STATE |
| | APPROVAL FOR THIS PRODUCT (WILL GIVE |
| | MIAMI-DADE NOA A LOCAL PROD. APPROVAL) |
| | B) GARAGE DOOR DESIGN PRESSURE DOES NOT |
| | MEET THE DESIGN PRESSURE IN THE DOOR |
| | SCHEDULE |
| | C) TIMBERLINE SELECT 40 SHINGLE NOA HAS |
| | BEEN REVISED (04-0305.04) |
| | D) KINCO NOA FOR SGD HAS EXPIRED SEE |
| | STATE APPROVAL CLICK ON PDF FILE AND |
| | PRINT INSTALLATION FOR 1X BUCK AND 2X |
| | BUCK BOTH ARE GOOD TO -70 PSF (FLORIDA |
| | SHEET OK) |
| | E) STATE PRODUCT APPROVAL DOES NOT COVER |
| | M40 XHP ONLY HP PLEASE SUBMIT REVISED |
| | MIAMI-DADE NOA (06-0413.06) FOR LOCAL |
| | PROD APPROVAL |
| | |
| | THOSE PRODUCTS WHICH ARE REGULATED BY |
| | DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | (PLEASE CHECK CORRECTED COPIES) |
| | |
| | 13)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT IS REQUIRED PRIOR TO |
| | A PERMIT BEING ISSUED |
| | |