| Plan Review Notes For Permit 06071487 |
| Permit Number |
06071487 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-07-26 00:00:00 | DENIED | | | | | | 1)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) THE PRODUCT APPROVAL NOA LISTS SIX | | | MAXIMUM DESIGN PRESSURES ON PAGE 8. | | | CIRCLE THE ONE THAT CORRESPONDS WITH THE | | | SYSTEM YOU ARE INSTALLING. BASED ON THE | | | DESCRIPTION OF WORK ON THE APPLICATION, | | | IT APPEARS THAT THE LAST ITEM APPLIES. | | | THE DESIGN PRESSURE FOR THAT ITEM (-45 | | | PSF) DOES NOT MEET THE REQUIRED ROOF | | | PRESSURES FOR THE STRUCTURE AND | | | LIMITATION #9 DOES NOT ALLOW ANY | | | INCREASES. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | | | | | | | |
|