| 2007-02-12 14:58:12 | |
| | |
| | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE THE REVISIONS SUBMTTED ARE T DATED |
| | 10/23/06., HOWEVER THERE ARE SEVERAL REVISIONS TO THE |
| | EXISTING DWELLING. PLANS INDICATE THE ENITER DWELLING |
| | BEING REWIRED. PLEASE SEE THAT ANY REVISIONS AFTER THAT |
| | DATE WOULD BE REFLECTED ON TITLE BLOCKS AND THEN THE |
| | PLANS LABELED WITH THE SAME NUMERICAL DESIGANTION. |
| | PLEASE CORRELATE AND SUBMIT REVISIONS AS NEEDED. |
| | 106.1, 106.3.5.4 |
| | |
| | 2) NOTE: PLEASE SEE THE PANEL SCHEDULE SUBMITED IS THE |
| | SAME AS THE PREVIOUS PANEL SCHEDULE ISSUED FOR PERMIT. |
| | PLEASE LABEL ALL NEW CIRCUITS, ARC FAULT FOR NEW WIRED |
| | BEDROOMS, DEDICATED FOR BATH, ETC |
| | 210.52, 210.12, 210.11C3. |
| | PLEASE SEE PANEL SCHEDULE SHALL BE ROOM AND AREA |
| | SPECIFIC. PLEASE SEE THE FOLLOWING TEXT EXTRACTED FROM |
| | THE CODE COMMENTARY. |
| | *CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| | CIRCUIT SUPPLIED BY A PANELBOARD OR SWITCHBOARD BE |
| | LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| | SUFFICIENT DETAIL REQUIRED BY THIS SECTION. |
| | 408.4, 310.16, 240.4 |
| | |
| | 3) NOTE: PLEASE SEE THAT AS THE SCOPE OF WORK FROM THE |
| | ORIGINAL PERMITTED SET OF PLANS HAS INCREASED, PLEASE |
| | ADJUST THE VALUE FROM THE APPLIED SCOPE OF WORK AND PAY |
| | ADDITIONAL FEES. |
| | PLEASE SEE THAT REVISED BUILDING SHOULD ALSO BE |
| | SUBMITTED FOR NEW WALL AREA. |
| | FBC 108.3 |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | DEWEY PALMER. |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |