| 2006-10-15 20:29:44 | ** UNSAT 2ND REVIEW *** |
| | |
| | PLEASE SEE ONE NOTE FROM PREVIOUS REVIEW AND NEW |
| | NOTE(S). |
| | |
| | 1) NOTE: PLEASE CORRELATE RISER AND PLANS. PLEASE SEE |
| | PLANS NOW SHOWS A J-BOX WHERE RISER SHOWS AND NEW MAIN |
| | DISCONNECT?? |
| | FBC 106.1.2, NEC 2002 |
| | |
| | 2) NOTE: PLEASE PLACE PLANS INTO TWO COMPLETE SETS |
| | ATTACHED AND BOTH SIGNED BY THE PERSON RESPONSIBLE FOR |
| | PLANS AND DESIGN. |
| | FBC 106.1.2, 106.1.3 |
| | |
| | 3) NOTE: PLEASE SEE A/ C LOAD IN LOAD CALCS STILL |
| | MENTIONS "COMP" , HOWEVER THE HEAT IS THE LARGER OF THE |
| | TWO LOADS. 220.21. |
| | PLEASE CORRELATE. |
| | |
| | 4) NOTE: PLEASE SEE ALL THREE COPIES OF SURVEY'S HAVE |
| | BEEN "VOIDED" AS THEY DO NOT CONTAIN AN ORIGINAL |
| | SIGNATURE AND SEAL AS REQUIRED UNDER FAC 61G17, FS |
| | 472.025. PLEASE SEE STATEMENT ON SURVEY EVEN SAYS NOT |
| | VALID W/OUT SEAL. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |