| 2006-08-09 00:00:00 | IN ELEC FOR REVIEW, IN PROGRESS. |
| | *** UNSAT **** |
| | |
| | 1) NOTE: PLEASE SEE CODE REFERENCED IN |
| | NOTES MENTIONS THE 1996 NEC? |
| | PLEASE SEE THIS SHOULD READ 2002 NEC. |
| | |
| | 2) NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52. (REDLINED) |
| | |
| | 3) NOTE: PLEASE SEE RISER DOES NOT SEEM |
| | TO CORRELATE WITH PLANS AND PANEL NOTE. |
| | PLEASE SEE RISER SHOWS THIS AS A NEW |
| | PROPOSED SERVICE WITH A NEW MAIN LOCATED |
| | OUTSIDE ,PLANS DO NOT SHOW ANY MAIN AND |
| | PANEL NOTE MENTIONS THIS IS EXSITING. |
| | PLEASE EXPLAIN HOW THE SERVICE IS |
| | EXISTING AS SHOWN AS THE ADDITION HAS |
| | NOT YET BEEN BUILT? |
| | PLEASE CORRELATE AND REVISE AS NEEDED. |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 4) NOTE: PLEASE SEE AN "EQUIPMENT |
| | GROUNDING CONDUCTOR" IS BEING SHOWN WITH |
| | THE SEC'S. PLEASE SEE 250.24B, 250.6 FOR |
| | OBJECTIONABLE CURRENTS AND THE |
| | "EQUIPMENT GROUNDING CONDUCTOR" BEING |
| | INSTALLED "AFTER" THE FIRST MEANS OF |
| | DISCONNECT. |
| | |
| | 5) NOTE: PLEASE SEE MISSING A/C CU |
| | DISCONNECT PER 440.11. |
| | |
| | 6) NOTE: PLEASE SE EMISSING GFI RECEPT |
| | FOR CU. 210.63,210.8A. |
| | |
| | 7) NOTE: PLEASE SEE LOAD CALCULATIONS |
| | WHICH INDICATE THE CU AT THE LOAD LARGER |
| | THAN HEAT AT 8KW, YET THE AHU'S HEAT IS |
| | THE 8KW WHICH IS LARGER. |
| | PLEASE ADJUST. |
| | PLEASE SEE 220.21, 220.30C |
| | |
| | 8) NOTE: PLEASE SEE MISSING KITCHEN |
| | COUNTER SPACE GFI RECEPT REQUIRED PER |
| | 210.52C1, 210.8A6 |
| | |
| | 9) NOTE: PLEASE SEE WALL SPACE IN |
| | KITCHEN WHICH IS 2' OR MORE IS REQUIRED |
| | TO CONTAIN A RECEPT. PLEASE SEE |
| | 210.52B1, 210.11C1, AS THIS IS REQUIRED |
| | OT BE ON ONE OR MORE OF THE SMALL |
| | APPLIANCE CIRCUITS. |
| | |
| | 10) NOTE: PLEASE SEE PLANS IDNICATE A |
| | NEW DISPOSAL, HOWEVER THIS COULD NOT BE |
| | LOCATED ON PANEL SCHEDULE OR IN LOAD |
| | CALCULATIONS. |
| | |
| | 11) NOTE: PLEASE SE MIN OCP FOR THE AHU |
| | SHALL BE SIZED AT 125% PER 424.3B. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. PLEASE DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS INNEW SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |