| 2006-08-18 00:00:00 | |
| | |
| | DENIED |
| | |
| | 1) THE CLAIMED VALUATION ON THE PERMIT |
| | APPLICATION IS LOW. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT |
| | COST EXCLUDING LAND VALUE. OUR VALUATION |
| | REFERENCE IS ICC (BVD), MARSHALL-SWIFT |
| | AND MEANS COST ANALYSIS SERVICES PER |
| | 108.3 FBC* |
| | |
| | 2) THE STATE OF FLORIDA REQUIRES |
| | COLLECTION OF A RADON SURCHARGE ON ALL |
| | NEW CONSTRUCTION COMPUTED ON UNDER ROOF |
| | FLOOR SPACE PER 10D-91 FAC. THESE FEES |
| | WILL BE ADDED TO THE PERMIT APPLICATION |
| | FEES |
| | |
| | 3) IN AREAS OF QUESTIONABLE SOILS AS |
| | SHOWN IN THE OFFICIAL ZONING MAP OF THE |
| | CITY OF WEST PALM BEACH, 2 COPIES OF A |
| | SOIL TEST REPORT SHALL BE SUBMITTED PER |
| | R401.4 |
| | |
| | 4) SUBMIT ENERGY CALC'S PER 13-101.2.2 |
| | FBC. BE SURE THAT THEY ARE SIGNED AND |
| | DATED BY PREPARER AND OWNER/AGENT PRIOR |
| | TO SUBMITTAL |
| | *****NOTE THE CALC'S THAT WERE SUBMITTED |
| | HAVE WRONG INFORMATION 8B IS NOT |
| | APPLICABLE BECAUSE FLOOR TYPE IS 8A AND |
| | WALL TYPE IS WOOD FRAME AND REQUIRES |
| | R-11, PLEASE CORRECT***** |
| | |
| | 5) CONTRACTOR DID NOT SIGN APPLICATION |
| | |
| | 6) PRODUCT APPROVAL FOR WINDOWS |
| | INCORRECT, FLORIDA COVER SHEET FOR |
| | TR-9100 WINDOWS NOT 240 AS MIAMI-DADE |
| | NOA. IF USING 240 WINDOWS THE CORRECT |
| | FL# IS 6738 AND THE MIAMI-DADE REPORT |
| | THAT ACCOMPANIES THE COVER IS 05-0930.03 |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |