Plan Review Notes
Plan Review Notes For Permit 06071436
Permit Number 06071436
Review Stop E
Sequence Number 3
Notes
Date Text
2007-04-10 11:33:55** NEEDS NEW RE-RECORDED NOC ONCE PERMIT IS READY FOR
 ISSUANCE. THE NOC HAS EXPIRED PER FS 713.13(2).
  
 ** REDLINED PLANS.
  
 ATS IS SE RATED AS SUBMITTED ON SPECS AND TAPS SHOULD
 BE MADE ON THE LOAD SIDE OF THE MAIN FOR AIC RATING
 PROTECTION OF MAIN. 110.9.
 STAMP FOR ELEC ONLY.
 NEEDS GAS AND ZONING REVIEWS.