| 2006-08-09 00:00:00 | ***** UNSAT **** |
| | |
| | 1) NOTE: PLEASE SEE THE 2002 NEC. |
| | 225.31-225.39, 230.72, 240.4, 310.16, |
| | 408.16, 408, 250.110, 250.122, 250.24B, |
| | 240.21 ETC |
| | PLEASE SEE THERE ARE MANY ITEMS MISSING |
| | AND/OR ARE NOT SHOWN FOR CODE |
| | COMPLIANCE. |
| | PLEASE VERIFY THE RISER WITH EQUIPMENT |
| | WHICH IS BEING SHOWN FOR USE. PLEASE SEE |
| | OCP ON GEN, RATINGS OF EQUIPMENT, |
| | MISSING DISCONNECTING MEANS FOR FEEDERS |
| | FROM GEN (MAY NOT USE BRKR ON UNIT), |
| | CONDUCTORS SIZING, EQUIPMENT USED AS |
| | RACEWAYS, GTOUNDING/EQUIPMENT GORUNDING |
| | CONDUCTORS. ETC. |
| | |
| | 2) NOTE: PLEASE SEE NEC 220 FOR LOAD |
| | CALCULATIONS WHICH ARE TO BE COMPLETED |
| | PER NEC. THE RESIDENTIAL USE IS NOT |
| | CLEAR AT THIS TIME, HOWEVER IN ANY CSE |
| | PLEASE COMPLETE ELECTRICAL CALCULATIONS |
| | FOR COMMERICAL LOADS ETC. |
| | 220.3,220.10,220.13,220.11 ETC |
| | PLEASE SEE 215.3,230.42 ETC |
| | |
| | 3) NOTE: PLEASE SEE RESIDENTIAL PANEL IS |
| | SHOWING AN AHU#9??? WHERE IS 1-8? |
| | NONE COULD BE LOCATED ON THESE PANEL |
| | SCHEDULE EXCEPT FOR TWO.?? |
| | |
| | 4) NOTE: PLEASE PROVIDE A LAYOUT OF ALL |
| | SERVICE EQUIPMENT. PLEASE PROVIDE AN |
| | OVERVIEW AS THE ONLY EQUIPMENT SHOWN WAS |
| | THE EXISTING 800A MAIN. |
| | |
| | 5) NOTE: PLEASE SEE ATS NEEDS TO BE |
| | HIGHLIGHTED ON SPECS FOR WHICH ONE IS |
| | BEING USED. PLEASE KNOW AS PER NOTES |
| | ABOVE, THE ATS THE WAY IT IS SHOWN DOES |
| | NOT MEET CODE. |
| | |
| | 6) NOTE: PLEASE SEE ALL PLANS, DESIGNS |
| | AND LOAD CALULATIONS SHALL CONTAIN A |
| | STATEMENT" DRAWN BY: PRINTED NAME AND |
| | SIGNATURE OF THE PERSON RESPSOSIBLE FOR |
| | SAID PLANS AND DESIGNS. |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE PROVIDE COPY OF CONTRACT |
| | FOR COMPLETE SCOPE OF WORK FOR THIS |
| | PERMIT. PLEASE SEE FBC 108.3 WHICH |
| | REQUIRES VALUE FOR ALL LABOUR AND |
| | MATERIALS EVEN IF ANY EQUIPMENT IS OWNER |
| | SUPPLIED. PLEASE KNOW, THE MARSHALL'S |
| | /SWIFT GUIDE MAY BE USED IN VALUATIONS |
| | BY THIS OFFICE AS ADOPTED BY THE FBC |
| | 2004. |
| | |
| | ** UNABLE TO DO A COMPLETE REVIEW AT |
| | THIS TIME. |
| | PLEASE BE SURE TO GO OVER PLANS AND |
| | RISER BEFORE RESUBMITTING. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |