2006-08-09 00:00:00***** UNSAT ****
  
 1) NOTE: PLEASE SEE THE 2002 NEC.
 225.31-225.39, 230.72, 240.4, 310.16,
 408.16, 408, 250.110, 250.122, 250.24B,
 240.21 ETC
 PLEASE SEE THERE ARE MANY ITEMS MISSING
 AND/OR ARE NOT SHOWN FOR CODE
 COMPLIANCE.
 PLEASE VERIFY THE RISER WITH EQUIPMENT
 WHICH IS BEING SHOWN FOR USE. PLEASE SEE
 OCP ON GEN, RATINGS OF EQUIPMENT,
 MISSING DISCONNECTING MEANS FOR FEEDERS
 FROM GEN (MAY NOT USE BRKR ON UNIT),
 CONDUCTORS SIZING, EQUIPMENT USED AS
 RACEWAYS, GTOUNDING/EQUIPMENT GORUNDING
 CONDUCTORS. ETC.
  
 2) NOTE: PLEASE SEE NEC 220 FOR LOAD
 CALCULATIONS WHICH ARE TO BE COMPLETED
 PER NEC. THE RESIDENTIAL USE IS NOT
 CLEAR AT THIS TIME, HOWEVER IN ANY CSE
 PLEASE COMPLETE ELECTRICAL CALCULATIONS
 FOR COMMERICAL LOADS ETC.
 220.3,220.10,220.13,220.11 ETC
 PLEASE SEE 215.3,230.42 ETC
  
 3) NOTE: PLEASE SEE RESIDENTIAL PANEL IS
 SHOWING AN AHU#9??? WHERE IS 1-8?
 NONE COULD BE LOCATED ON THESE PANEL
 SCHEDULE EXCEPT FOR TWO.??
  
 4) NOTE: PLEASE PROVIDE A LAYOUT OF ALL
 SERVICE EQUIPMENT. PLEASE PROVIDE AN
 OVERVIEW AS THE ONLY EQUIPMENT SHOWN WAS
 THE EXISTING 800A MAIN.
  
 5) NOTE: PLEASE SEE ATS NEEDS TO BE
 HIGHLIGHTED ON SPECS FOR WHICH ONE IS
 BEING USED. PLEASE KNOW AS PER NOTES
 ABOVE, THE ATS THE WAY IT IS SHOWN DOES
 NOT MEET CODE.
  
 6) NOTE: PLEASE SEE ALL PLANS, DESIGNS
 AND LOAD CALULATIONS SHALL CONTAIN A
 STATEMENT" DRAWN BY: PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPSOSIBLE FOR
 SAID PLANS AND DESIGNS.
 FBC 106.1.2
  
 7) NOTE: PLEASE PROVIDE COPY OF CONTRACT
 FOR COMPLETE SCOPE OF WORK FOR THIS
 PERMIT. PLEASE SEE FBC 108.3 WHICH
 REQUIRES VALUE FOR ALL LABOUR AND
 MATERIALS EVEN IF ANY EQUIPMENT IS OWNER
 SUPPLIED. PLEASE KNOW, THE MARSHALL'S
 /SWIFT GUIDE MAY BE USED IN VALUATIONS
 BY THIS OFFICE AS ADOPTED BY THE FBC
 2004.
  
 ** UNABLE TO DO A COMPLETE REVIEW AT
 THIS TIME.
 PLEASE BE SURE TO GO OVER PLANS AND
 RISER BEFORE RESUBMITTING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  