| Date |
Text |
| 2007-09-29 07:47:24 | |
| | |
| | |
| | DENIED |
| | |
| | THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM THE 2ND |
| | REVIEW PERFORMED ON 6/7/07 : |
| | |
| | 1) PER FLORIDA STATUTE 481.229 EXEMPTION FROM |
| | ARCHITECTURAL LICENSURE ONLY APPLIES TO 1 FAMILY AND 2 |
| | FAMILY RESIDENCES (R3) NOT MULTI FAMILY (R2)OR |
| | RENOVATIONS OVER $25,000, THEREFORE DRAWINGS ARE |
| | REQUIRED TO BE DRAWN BY A LICENSED DESIGN |
| | PROFESSIONAL. |
| | ****DRAWINGS TO BE SIGNED AND SEALED BY DESIGNER OF |
| | RECORD**** |
| | |
| | 2)WHERE SPECIAL CONDITIONS EXIST, THE BUILDING |
| | OFFICIAL IS AUTHORIZED TO REQUIRE ADDITIONAL |
| | CONSTRUCTION DOCUMENTS TO BE PREPARED BY A DESIGN |
| | PROFESSIONAL PER 106.1 FBC |
| | ****RATED WALLS BETWEEN UNITS AND COMMON AREAS WILL |
| | HAVE WORK PERFORMED AND REQUIRE RATED ASSEMBLY DETAILS |
| | ON THE DRAWINGS**** |
| | |
| | 4)WORK ON EXISTING BUILDINGS IS COVERED UNDER THE FBC |
| | (EXISTING) AS SUCH A DESIGN PROFESSIONAL OR OWNERMUST |
| | ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION PER |
| | 301.5 FBC (EXISTING) |
| | ****THIS APPEARS TO BE AT MINIMUM A LEVEL 2 |
| | ALTERATION**** |
| | |
| | 5)CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION,NATURE, AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE PER 106.1.1 |
| | FBC* |
| | ****DRAWINGS SHALL BE COMPLETE AND SHOW ENTIRE UNIT, |
| | ALL DEMO WORK AND NEW FLOOR PLAN, FIRE RARED WALL |
| | DETAILS, COMPLIANCE WITH 604.4.3 FBC EXISTING**** |
| | |
| | 7)PROVIDE COMPLETE PERMIT APPLICATION, 2ND PAGE IS |
| | MISSING. |
| | ****THIS PAGE CONTAINS THE CONTRACTOR/AGENT SIGNATURE |
| | INFORMATION**** |
| | |
| | 8)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT IS REQUIRED PRIOR TO |
| | A PERMIT BEING ISSUED |
| | |
| | *******NEW COMMENTS****** |
| | |
| | 1)PROVIDE 2 COMPLETE SETS OF DRAWINGS FOR PERMIT |
| | APPLICATION THEY SHALL CONTAIN AT MINIMUM, DEMO FLOOR |
| | PLAN, NEW FLOOR PLAN, PLUMBING, ELECTRICAL AND |
| | MECHANICAL IF CHANGES ARE MADE, ALSO DETAILS FOR FIRE |
| | RATED WALLS AND ANY REPAIRS. PROVIDE LAYOUT OF ENTIRE |
| | UNIT TO SHOW SMOKE ALARM COMPLIANCE. |
| | |
| | 2)NEW PLUMBING AND ELECTRICAL DRAWINGS SHOW WORK |
| | PERFORMED ON THE UNIT SEPARATION WALL (RATED) IS WALL |
| | FURRED OUT OR ARE RATED WALLS PENETRATED. |
| | |
| | 3)PROVIDE MECHANICAL DRAWING FOR NEW RANGE HOOD |
| | DUCTING TO EXISTING RATED SHAFT AND ANY NEW A/C |
| | RECONFIGURATION |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |