Plan Review Notes
Plan Review Notes For Permit 06071423
Permit Number 06071423
Review Stop P
Sequence Number 2
Notes
Date Text
2007-06-05 15:59:21DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLANS ARE NOT ACCEPTABLE PER FBC-2004 CHAPTER 1,
 SECTION 106.1.1 AND 106.1.3. DRAWINGS SUBMITTED IN
 PENCIL ARE UNACCEPTABLE. (REFERENCE THE ATTACHED BATH
 DEMO)
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3
 PLUMBING (3), (5): A WATER ISOMETRIC RISER DIAGRAM
 (INCLUDING BOTH HOT AND COLD WATER) WITH SIZES, WATER
 HAMMER ARRESTORS AND VALVE LOCATIONS REQUIRED FOR THE
 PLUMBING CHANGES. PLEASE INDICATE IF WATER HEATER IS
 EXISTING OR NEW. IF WATER HEATER IS NEW A WATER HEATER
 DETAIL IS REQUIRED.
  
 3. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3
 PLUMBING (4), (6): PLEASE SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL WASTE, VENTS,
 TRAPS AND SIZES WITH CLEANOUT LOCATIONS OF THE PLUMBING
 CHANGES.
  
 4. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3
 PLUMBING (10):THE LOCATION OF THE WATER SUPPLY LINE
 IS REQUIRED FOR THE PLUMBING CHANGES.
  
 5. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS REVIEWER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721