| Notes |
| Date |
Text |
| 2007-05-17 09:06:20 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE DESIGNER OF RECORD MUST PRINT AND SIGN THEIR | | | NAME TO PLANS PER 106.3.4.3. FBC. | | | | | | 2 } THE ORIGINAL SHEET THAT WAS REVIEWED FOR NEC | | | COMPLIANCE , AND THE DESIGNERS SIGNATURE (WHICHIS A | | | COPY) MUST BE RETURNED TO THE DESIGNER FOR NEW SHEETS. | | | | | | 3} THE BATH PLAN THAT IS STAPLED TO THE ORIGINAL PLAN | | | DOES NOT SHOW COMPLIANCE WITH RECEPTACLE REQUIREMENTS. | | | BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE PER | | | 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI | | | PROTECTED PER 210.8(A) (1). | | | | | | 4}SEE 13-606.1.ABC.1.2.3 FBC FOR REQUIREMENTS FOR | | | RECESSED LIGHTING FIXTURES. INDICATE COMPLIANCE WITH | | | SAME. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | | | | | | | |
|