| 2006-08-18 00:00:00 | **** UNSAT *** |
| | |
| | 1) NOTE: PLEASE CORRELATE RISER WITH |
| | INFORMATION FOR PANELS AND MAINS. |
| | PLEASE SEE RISER SHOWS ONE SIZE FOR THIS |
| | MAINS AND PANELS, AND THE PANELS SHOW A |
| | DIFFERENT SIZE. |
| | PLEASE COMPLETE RISER DIAGRAM AT HOUSE, |
| | AS THE PANEL IS NOT SHOWN WITH |
| | CONDUCTORS, CONDUITS ETC. |
| | PLEASE SUBMIT PANEL SCHEDULES FOR ALL |
| | MINIMUM REQUIRED CIRCUITS PER NEC. |
| | PLEASE SEE SEC'S ARE NOT LARGE ENOUGH |
| | FOR LOAD CALCULATIONS SHOWN. |
| | PLEASE COMPLETE GROUNDING ELECTRODE |
| | SYSTEM AT SERVICE AND AT MAIN HOUSE. |
| | PLEASE SEE THAT PLANS ARE NOT COMPLETE |
| | AT THIS TIME. |
| | PLEASE SEE; |
| | 210.11,220.16,210.11C1,C2, C3, , |
| | 240.4,310.16, 408.4, 215.5, 250.32, |
| | 250.50, 220.31, 210.12, 210.52B1, ETC |
| | ETC. |
| | |
| | 2) NOTE: PLEASE KNOW WHEN PLANS ARE NOT |
| | DONE BY AN ARCHITECT OR ENGINEER AND |
| | SCOPE OF WORK DOES NOT REQUIRE THIS, |
| | PLANS STILL MUST CONTAIN THE PRINTED |
| | ANDME AND SIGNATURE OF THE PERSON TAKING |
| | RESPONSIBILITY OF PLANS AND DESIGN/ |
| | PLANS ONLY CONTAIN THE PRINTED NAME. |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE ZONING COMMENTS AS |
| | THIS WILL AFFECT ELECTRICAL RISER AND |
| | DESIGN. |
| | |
| | 4) NOTE: PLEASE SEE ELECTRICAL RISER AS |
| | SHOWN ON PLAN LAYOUT SEEMS TO BE LOCATED |
| | OFF THE BUILDING, PLEASE INDICATE IF |
| | SERVICE IS BEING BUILT DETACHED FROM |
| | STRUCTURE. IF SO, PLEASE SEE |
| | 225.31-225.39 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |