Plan Review Notes
Plan Review Notes For Permit 06071405
Permit Number 06071405
Review Stop B
Sequence Number 2
Notes
Date Text
2006-08-01 00:00:00DENIED
  
 1) SPECIFY HOW THE ROOF PRESSURES FOR
 THE PERIMETER AND END ZONES WERE
 DETERMINED. SUBMIT THE SIGNED AND SEALED
 CALCULATIONS OR THE WIND TUNNEL TEST
 REPORT USED TO DETERMINE THE ROOF
 PRESSURES. SEE FIRST REVIEW.
  
 2) SUBMIT SIGNED AND SEALED RAS 117
 CALCULATIONS FOR ENHANCED FASTENING. SEE
 ITEM 2 ON FIRST REVIEW.
  
 3) THE COVERSHEET WITH THE FL# THAT WAS
 SUBMITTED IS NOT THE ONE THAT
 CORRESPONDS WITH NOA 03-0501.03. THE
 CORRECT ONE IS FL#617-R1. PLEASE SUBMIT
 THE CORRECT ONE.
  
 4) FROM THE INFORMATION THAT WAS
 SUBMITTED IT APPEARS THAT ONLY A THREE
 FOOT WIDE ARE AT THE PERIMETER OF THE
 ROOF AND THE PARAPETS ARE BEING
 REROOFED. IS THIS CORRECT?
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  