| Plan Review Notes For Permit 06071405 |
| Permit Number |
06071405 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-07-25 00:00:00 | DENIED | | | | | | 1) SUBMIT THE ROOF PRESSURES FOR ZONES | | | 1,2 AND 3 OF THE 15 STORY STRUCTURE. | | | SPECIFY HOW THESE PRESSURES WERE | | | DETERMINED(PROVIDE CALCULATIONS OR WIND | | | TUNNEL TEST REPORT). SPECIFY THE MEAN | | | ROOF HEIGHT AND EXPOSURE CATEGORY. | | | | | | 2) SUBMIT SIGNED AND SEALED RAS 117 | | | CALCULATIONS FOR THE FASTENER DENSITIES | | | WHICH INDICATE THAT THE REQUIRED UPLIFT | | | PRESSURES WILL BE MET FOR THE VARIOUS | | | ROOF ZONES. | | | | | | 3) SUBMIT A COVERSHEET FROM THE STATE | | | PRODUCT APPROVAL WEBSITE WITH THE FL# | | | FOR THE ROOFING PRODUCT THAT WILL BE | | | INSTALLED. SEE WWW.FLORIDABUILDING.ORG. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|