| Plan Review Notes For Permit 06071403 |
| Permit Number |
06071403 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-07-28 00:00:00 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED | | | BY OWNER/AGENT, PER 2004 FBC | | | 13-600.3.ABC.2 | | | | | | 2) JOB ADDRESS NEEDS TO BE ON ALL PLANS | | | (ALL PAGES) . | | | | | | 3) TWO 10" RETURN AIR DUCTS IS NOT | | | ENOUGH FOR A 3 1/2 TON SUSTEM WITH A 16" | | | SUPPLU AIR DUCT, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|