| 2007-02-01 08:24:45 | *** DENIED *** |
| | |
| | 1) AS NOTED IN LAST REVIEW 10-24-07 NOTE #2, MECHANICAL |
| | PLANS FOR MAIN GUEST HOUSE, NEED JOB ADDRESS ON THEM. |
| | |
| | 2) AS NOTED IN LAST REVIEW 10-24-07 NOTE #3, THE A/C |
| | SYSTEM FOR THE MAIN HOUSE IS OVER-SIZED, THE MAIN HOUSE |
| | MANUAL J CALCULATIONS ARE CALLING FOR 19,578 SENSIBLE |
| | BTU'S, THE MECHANICAL PLANS ARE CALLING FOR 33,322 |
| | SENSIBLE BTU'S, THE PLANS CAN ONLY CALL FOR 20% MORE |
| | THAN THE MANUAL J CAL'S, PER 2004 FBC 13-607.1.ABC.1.1, |
| | PLEASE CORRECT. |
| | |
| | 3) SEE MAIN HOUSE MECH. PLAN, 12"RETURN AIR TRANSFER |
| | DUCT TO MASTER SUITE IS TO SMALL. BALANCED RETURN AIR |
| | MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE |
| | RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS |
| | SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR |
| | HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO |
| | ACHIEVE PROPER RETURN AIR BALANCE. |
| | (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET |
| | THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR |
| | EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY |
| | ROOMS, |
| | EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL |
| | BE INCLUDED. PER 2004 FBC/R M1602.4. |
| | |
| | 4) PLEASE SHOW ON MECHANICAL PLANS WERE THE CLOTHES |
| | DRYER VENT WILL TERMINATE (VENT MAY NOT DISCHARGE NEAR |
| | A/C CONDENSER UNIT). |
| | |
| | 5) SEE MECHANICAL PLANS TO MAIN HOUSE, WHITE-OUT MAY |
| | NOT BE USED ON PLANS, AND DO NOT SUBMIT CHANGES IN PEN. |
| | PLEASE MAKE COPY'S AFTER CHANGES HAVE BEEN MADE AND |
| | SUBMIT COPY'S. |
| | |
| | 6) ONE SET OF PLANS TO MAIN HOUSE HAS TWO DIFFERENT |
| | MECHANICAL PLANS, PLEASE REMOVE ONE. |
| | |
| | 7) SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR |
| | TIMES THE FEE. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |