| 2006-10-26 17:38:45 | BUILDING REVIEW 2ND CHECKLIST: |
| | |
| | 1- ENERGY CALCULATIONS:REVISE INFORMATION ON TOP OF |
| | FORM.NEED CORRECT ADDRESS,NAME OF BUILDER AND |
| | PERMITTING OFFICE. |
| | |
| | 2- ENGINEER TO CLARIFY WHY ARE THERE 2 DIFFERENT ZIP |
| | CODES ON HIS ADDRESS. SEE ADDRESS ON DRAWING TITLE |
| | BLOCK (33314)AND ADDRESS ON RUBBER STAMP (33440) . |
| | WHICH ONE IS THE CORRECT ONE. REVISE AS REQUIRED. |
| | |
| | 3- PROVIDE FLORIDA OR LOCAL PRODUCT APPROVAL AS |
| | REQUIRED BY DCA RULE 9B-72 FOR: |
| | A) SINGLE HUNG WINDOWS. DADE COUNTY NOA #05-0112.01 |
| | SUBMITTED EXPIRED ON 10/08/06. NEED CURRENT ONE. |
| | ***NOTE: ENGINEER OF RECORD TO REVIEW AND APPROVE |
| | CURRENT NOA. |
| | B) PRECAST CONCRETE LINTELS. |
| | ***NOTE: ENGINEER TO REVIEW IT AND APPROVE IT AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 4- CLARIFY WHY EDGE DETAIL FOR GARAGE AND SHOWER STEP |
| | DOWN SHOW NO REINFORCEMENT.SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 5- SHEET T1: |
| | A) SPECIFY CONNECTORS AT THE ENDS OF DOUBLE 2X12 |
| | WOOD BEAM WHEN RESTING ON THE MASONRY WALL. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | B) REVISE STRUCTURAL NOTE #3.STAPLEWITH 7/8 LEGS |
| | IS NOT ALLOWED. SEE ASTM C926 AND ASTM C1063. NEED MIN. |
| | 1 3/4" PENETRATION INTO THE THE TRUSS. REVISE AS |
| | REQUIRED. |
| | |
| | 6- STORM SHUTTERS: |
| | A) THERE ARE 2 DIFFERENT PRODUCT APPROVALS |
| | SUBMITTED. SUBMIT ONLY ONE TYPE. |
| | B) IF USING FLORIDA PRODUCT APPROVAL FL240, THEN |
| | PROVIDE FLORIDA COVER PAGE FOR 2004 VERSION. GO TO |
| | WWW.FLORIDABUILDING.ORG TO DOWNLOAD ALL INFORMATION. |
| | |
| | C) IF USING FL5870, THEN MARK ON DRAWINGS SPECIFIC |
| | ANCHOR TYPE AND SPACING TO BE USED AS DONE WITH |
| | DRAWINGS FOR FL240. TO VERIFY COMPLIANCE WITH PRODUCT |
| | APPLICATION. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | D) PLEASE MAKE SURE ALL DRAWINGS ARE CLEAR AND |
| | LEGIBLE. |
| | |
| | ***NOTE: PLEASE MAKE SURE SELECTED PRODUCT IS REVIEWED |
| | AND APPROVED BY THE ENGINEER OF RECORD. |
| | |
| | 7- CONTRACTOR TO UPDATE WORKERS COMPENSATIONAND |
| | LICENSE INFORMATION WITH PERMIT CLERK. |
| | |
| | 8- TRUSS LAYOUT SUBMITTED. NEED COMPLETE TRUSS PACKAGE |
| | INCLUDING THE INDIVIDUAL TRUSSES. THIS INFORMATION NEED |
| | NO BE SUBMITTED NOW, BUT IT NEEDS TO BE SUBMITTED FOR |
| | REVIEW PRIOR TO INSTALLATION. SEE SEC. R802.10 FOR |
| | REQUIRED INFORMATION TO BE SUBMITTED. |
| | |
| | 9- INDICATE ON SITE PLAN (OR SURVEY) HOW COMPLIANCE |
| | WITH SEC. R401.3 2004 FLORIDA RESIDENTIAL CODE IS |
| | ACHIEVED. |
| | |
| | 10- ALL DRAWINGS NEED TO HAVE THE ADDRESS OF PROPOSED |
| | PROJECT. |
| | |
| | 11- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS OF |
| | BEING RECORDED IF WORK IS NOT STARTED. NEED RE-RECORDED |
| | NOTICE OF COMMENCEMENT. SEC. 713.13(2) FLORIDA |
| | STATUTES. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |