| Plan Review Notes For Permit 06071373 |
| Permit Number |
06071373 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-10-25 14:49:35 | DENIED; | | | COMMENTS NOT ADDRESSED ON LAST REVIEW; | | | 1. QUEST HOUSE NOT ON SANITARY RISER DIAGRAM (2ND | | | REQUEST) | | | 2. WATER SEVICE ONE METER OR TWO SHOW ON PLANS. IF | | | ONE METER A BACKFLOW PREVENTER IS REQUIRED. (2ND | | | REQUEST) | | | 3. OK | | | 4.THERMAL EXPANTION CONTROL REQUIRED ON WATER HEATERS | | | IF BACKFLOW PREVENTOR IS INSTALLED (2ND REQUEST) |
|