Plan Review Notes
Plan Review Notes For Permit 06071373
Permit Number 06071373
Review Stop M
Sequence Number 2
Notes
Date Text
2006-10-24 11:55:21*** DENIED ***
 1) MECHANICAL PLANS NEED THE NAME AND SIGNATURE OF THE
 DESIGN PERSON ON THEM, FOR MAIN HOUSE AND COTTAGE. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE
 FOR THE DESIGN. PER FBC 104.2.1 .
  
 2) SEE MECHANICAL PLANS FOR MAIN HOUSE AND COTTAGE,
 NEED JOB ADDRESS ON THEM.
  
 3) THE MAIN HOUSE MANUAL J CALCULATIONS ARE CALLING FOR
 13,909 TOTAL SENSIBLE BTU'S, THE MECH. PLANS ARE
 CALLING FOR 33,322 TOTAL SENSIBLE BTU'S, THE PLANS CAN
 ONLY CALL FOR 20% MORE THAN THE MANUAL J CAL'S, PRE
 2004 FBC 13-607.1.ABC.1.1, PLEASE CORRECT.
  
 4) SEE MAIN HOUSE MECH. PLAN, PLEASE SHOW SIZE OF THE
 SUPPLY AIR DUCTS GOING TO THE TWO BATHROOMS.
  
 5) SETS OF PLANS ARE MIXED-UP PAGES FOR THE COTTAGE ARE
 IN WITHTHE SET FOR THE MAIN HOUSE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.