| Notes |
| Date |
Text |
| 2006-10-24 11:55:21 | *** DENIED *** | | | 1) MECHANICAL PLANS NEED THE NAME AND SIGNATURE OF THE | | | DESIGN PERSON ON THEM, FOR MAIN HOUSE AND COTTAGE. ALL | | | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING | | | DATA SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE | | | FOR THE DESIGN. PER FBC 104.2.1 . | | | | | | 2) SEE MECHANICAL PLANS FOR MAIN HOUSE AND COTTAGE, | | | NEED JOB ADDRESS ON THEM. | | | | | | 3) THE MAIN HOUSE MANUAL J CALCULATIONS ARE CALLING FOR | | | 13,909 TOTAL SENSIBLE BTU'S, THE MECH. PLANS ARE | | | CALLING FOR 33,322 TOTAL SENSIBLE BTU'S, THE PLANS CAN | | | ONLY CALL FOR 20% MORE THAN THE MANUAL J CAL'S, PRE | | | 2004 FBC 13-607.1.ABC.1.1, PLEASE CORRECT. | | | | | | 4) SEE MAIN HOUSE MECH. PLAN, PLEASE SHOW SIZE OF THE | | | SUPPLY AIR DUCTS GOING TO THE TWO BATHROOMS. | | | | | | 5) SETS OF PLANS ARE MIXED-UP PAGES FOR THE COTTAGE ARE | | | IN WITHTHE SET FOR THE MAIN HOUSE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|