| Plan Review Notes For Permit 06071373 |
| Permit Number |
06071373 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-07-26 00:00:00 | DENIED; | | | 1.PLEASE INCLUDE GUEST HOUSE ON THE | | | PLUMBING SANITARY RISER DIAGRAM. | | | 2.IS WATER SERVICE OFF ONE METER? IF SO | | | A BACKFLOW PREVENTOR IS REQUIRED TO BE | | | INSTALLED AT WATER METER. | | | 3.IS WATER HEATER IN MAIN HOUSE THE HOT | | | WATER SUPPY FOR THE GUEST HOUSE? IF SO | | | PLEASE SHOW ON PLAN THE DISTANCE FROM | | | WATER HEATER TO LAST FIXTURE IN GUEST | | | HOUSE. IF 100' A METHOD OF MAINTAINING | | | THE TEMPERATURE IN ACCORDANCE WITH | | | CHAPTER 13 OF THE FBC-2004. | | | 4.IF A BACKFLOW IS INSTALLED IN THE | | | WATER SYSTEM SYSTEM THEN A MEANS OF | | | THERMAL EXPANSION SHELL BE REQUIRED | | | PLEASE SHOW ON DRAWINGS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|